3.4 Multiple fans on steel chimney

 

y

If two or more chimney fans are required to create sufficient draft, installation 

procedures are the same as for single fan installation on a steel chimney. The 

only difference is that the fans are sitting next to each other on the top of the 

chimney. A special adapter plate is required.

 

y

When installing multiple fans, it is extremely important that the fans are of 

the same model and size, and they must be controlled in tandem by one (1) 

motor speed control. 

3.5 Multiple fans on a brick chimney – Oversized flue

 

y

If two or more fans are required to create sufficient draft, a special adapter 

plate is required. The adapter plate should be made of stainless steel (14 GA 

or thicker), depending on the size and the fan models used.

 

y

The two holes in the plate should match the throat diameter of the fan 

model used and the distance from center to center should be at least equal 

to the fan width (dimension 

B

 in 2.1. Dimensional Data).

 

y

The adapter should be sealed with silicone and bolted onto the top. When 

installing multiple fans, it is extremely important that the fans are of the 

same model and size, and they must be controlled in tandem by one (1) 

motor speed control. 

 

y

A similar approach should be taken if the flue size exceeds the fan base 

dimensions. The adapter plate should be sized so it covers the flue and 

secured. A hole should be cut in the center of the plate and the fan mounted 

centered over the hole.

3.6 Installation for high temperatures

 

y

if the fan is used for applications where the flue gas temperatures exceed  

400 °F at the flue exit, and does not exceed 650 °F, dilution bolts must be 

used. 

 

y

Dilution bolts will cause cool air to dilute the warm flue gas, by lifting the fan 

and leaving space so the cool air can get in under the fan base.

 

y

The dilution bolts should be installed in the outer holes in the fan base.

 

y

The dilution bolts are adjustable and should be adjusted so the flue gas 

temperature does not exceed 400 °F when discharged through the fan. When 

using dilution bolts the fan’s actual capacity is reduced and a stronger model 

may be required. The fiber mat is not required when using dilution bolts

8

3000270  RS gas and oil 20210818 - international

Summary of Contents for RS 009

Page 1: ...ation Chapters 1 2 Mechanical installation Chapter 3 Electrical installation Chapter 4 Start up and configuration Chapter 5 Maintenance and troubleshooting Chapter 6 READ AND SAVE THESE INSTRUCTIONS R...

Page 2: ...g place 5 This unit must be grounded How to use this manual This installation manual does not contain any system design documentation System design documentation is available from exodraft Accessories...

Page 3: ...ney fan must be interlocked with the connected appliance s to insure proper combustions and to avoid flue gas spillage 1 2 Shipping The packing list attached to one of the packages clearly lists all i...

Page 4: ...4 422 478 C in 10 8 13 5 15 5 17 4 mm 275 344 395 441 D in 3 0 3 3 3 9 3 9 mm 75 85 100 100 E in 9 4 11 6 13 5 15 4 mm 238 294 342 391 Temperature Rating Interm 575 F 300 C Cont 482 F 250 C Capacity 1...

Page 5: ...st be provided for combustion otherwise improper operation and inadequate venting of deadly flue gases may result Support system for the exodraft chimney fan Prior to installation of the chimney fan i...

Page 6: ...hroat of the fan the hole in the fiber mat should correspond to the throat Step 2 Preparation of fan y Locate the installation brackets in the grooves on the underside of the fan base using the bolts...

Page 7: ...that the bolts shall be installed from the bottom side in the two inner holes y Adjust the final position of the brackets ensuring that there is clearance between the brackets and the flue wall If the...

Page 8: ...e and bolted onto the top When installing multiple fans it is extremely important that the fans are of the same model and size and they must be controlled in tandem by one 1 motor speed control y A si...

Page 9: ...lation of Proven Draft Switch PDS y A safety system must be interlocked with the appliance s The safety system could utilize a Proven Draft Switch a thermal switch or a flow switch The device must be...

Page 10: ...same temperature rating Otherwise insulation may melt or degrade exposing bare wire 4 2 Wiring diagram for single fan with fan speed control The wiring diagram below shows the wiring of the chimney fa...

Page 11: ...ng must be in flexible or rigid metal conduit LEGEND 24 VAc 120 VAC WEATHERPROOF BOX N FAN SPEED CONTROL ORANGE RED WHITE BLACK GREEN FAN MOTOR WEATHERPROOF BOX ORANGE WEATHERPROOF BOX L 24V GAS VALVE...

Page 12: ...here in the system Check the system for flue gas spillage Mark this setting on the fan speed control cover 5 3 Adjusting the Proven Draft Switch setting y Remove the snap on cover from the conduit enc...

Page 13: ...housing unless power to the chimney fan has been disconnected 6 3 Chimney cleaning intervals It is extremely important to keep the chimney flue clean from products of combustion and deposits Soot can...

Page 14: ...eed control There is power to the fan but it hums and does not turn The motor run capacitor may be bad Creosote may stick Check capacitor and replace if necessary Clean fan The fan seems to work fine...

Page 15: ...Notes 15 3000270 RS gas and oil 20210818 international...

Page 16: ...www exodraft com Notes...

Reviews: