1.3.4 Requirements for duct system
Silencers
The duct system must be fitted with silencers specified by the Project Manager,
which meet the requirements of the operating area.
Bends
A duct bend may be fitted immediately after the unit, because the airflow in the
spigot has a uniformly moderate speed profile, which results in negligible system
pressure loss.
Insulation
The duct system must be insulated against:
● condensation
● sound leakage
● heating/cooling losses
Condensation
Condensation in the ducts may occur when the exhaust/outdoor air has high hu-
midity. EXHAUSTO recommends a condensation outlet is also fitted at the lowest
point in the ducts.
Outdoor air intake
The outdoor air intake must be dimensioned with sufficiently low airflow to prevent
rain and snow being drawn into the duct system.
No duct connection
If one or more of the spigots is not connected to a duct: Fit a
protective net to the spigots with a maximum mesh width of 20
mm.
3004504-2019-08-29
Product information
9/32