Motor damper
Motor damper type
LS (closing damper)
LSR (closing damper,
spring return)
Type
LS500-24
LSR500-24
Designation
LSA/LSF
LSFR
Motor type
NM24-F
AF-24
Rotation time
75–150 s
open: 150 s
close: 16 s
Ingress protection
IP42
IP42
Ambient temperature
-20ºC to +50ºC
-30ºC to +50ºC
Damper depth
100 mm
100 mm
A maximum of two LSFR dampers or four LSA/LSF dampers may be connected.
6.2 Panel filters
Data
VEX160
Device
ePM
10
50%
ePM
1
55%
Dimensions: h x w, 1 item per air direction
700 x 838
mm
Panel filter thickness
96
mm
Temperature resistant to
70
°C
Filter class according to ISO 16890
ePM
10
50%
ePM
1
55%
Filter class according to EN 779
M5
F7
Final pressure drop
For the final pressure drop over the filter, the lower of the following two methods is
recommended.
● Final pressure drop = 3 x initial pressure drop
● Final pressure drop = initial pressure drop + 100 Pa