6. Technical data
6.1 Weight, corrosion class, temperature ranges, etc.
Weight
VEX total weight
360 kg
Doors
2 x 24 kg
Crossflow heat exchanger
51 kg
Fan unit
2 x 26 kg
VEX for transporting into building (without doors, heat exchanger
and fan unit)
209 kg
Corrosion class
Corrosion class
Corrosion class C4 in accordance with EN ISO 12944-2
Temperature ranges
Outdoor air temperature
-40ºC to +35
℃
Ambient temperature
-30ºC to +50ºC
At temperatures below -25˚C (with outdoor installation), use of a thermostatically
controlled heater in the automated control box is recommended.
HMI-panel
Ingress protection
IP20
Ambient temperature
0°C - +50°C
At temperatures below 0˚C the display may react more slowly than usual.
Fire thermostats
Cut-out temperature, BT70
70°C
Cut-out temperature, BT50
50°C
Cut-out temperature, BT40
40°C
Max. ambient temperature, sensor
250°C
Ambient temperature, thermostat housing
0°C - +80°C
Sensor length
125 mm
Ingress protection
IP40
Temperature drop before reconnection possible min. 15°K
3004504-2019-08-29