64
Test Condition
Derating
Forced Air Cooling
Applies to CoolX600 and
Standard CoolX Modules
fitted in CoolX600
Performance of Bulk and
Dual modules to be
confirmed
0 m/s Linear Airflow:
Derate by 1.67%/
ᵒ
C above
40
ᵒ
C ambient
0.533 m/s Linear Airflow:
Derate by 2.14%/
ᵒ
C above
50
ᵒ
C ambient
1.067 m/s Linear Airflow:
Derate by 3%/
ᵒ
C above
60
ᵒ
C ambient
1.67 m/s Linear Airflow:
Derate by 5%/
ᵒ
C above
70
ᵒ
C ambient
CoolX1800
Test Condition
Derating
Normal Operation
Applies to CoolX1800 and
all CoolX Modules fitted in
CoolX1800
Derate by 2.5%/
ᵒ
C above
50
ᵒ
C ambient
Max ambient operating
temperature for a
CoolX1800 fitted with an
IEC AC input connector is
60
ᵒ
C
Max ambient operating
temperature for a
CoolX1800 fitted with a
Screw Terminal AC input
connector is 70
ᵒ
C