9

5.3.1  Access

Access to the listener configuration menu is
obtained by operating the 

P

 and 

E

 buttons

simultaneously.  If the BA644DF-P listener
configuration menu is not protected by an access
code the first parameter 'SCAn’ will be displayed.
If the BA644DF-P is protected by an access code,
‘CodE’ will be displayed first.  Pressing 

P

 will allow

the four digit security code to be entered digit by
digit using the 

 or 

 button to adjust the flashing

digit and 

P

 to move control to the next digit.  When

the correct code has been entered, pressing 

E

 will

cause the first parameter ‘SCAn’ to be displayed.
If an incorrect code is entered, or no button is
pressed for ten seconds, the indicator will
automatically return to the display mode.

Section 5.3.2 contains a summary of each
configuration function including a cross reference
to a more detailed description.

5.3.2 Summary of listener configuration
functions

   

Instrument          Summary

   

display               of function

‘SCAn’

Scan fieldbus segment 

Identifies

 

all data sources on the

fieldbus segment to which the listener is
connected and enables selected data to
be allocated to one of the eight listener
inputs in-1 to in-8.
See section 5.4.1

‘LiSt’

List configured input parameters

For each of the eight BA644DF-P
listener inputs, in-1 to in-8 shows if the
input is enabled, Source Address,
Destination Address and the Index
which have been allocated.
Parameters can not be changed from
within this function.
See section 5.4.2

‘Edit’

Enter addresses and display
parameters

Sub-menu which allows known fieldbus
device addresses to be entered and all
display parameters adjusted for each of
the eight fieldbus listener inputs.
See section 5.4.3

 

‘Enb’

Enable selected input

Enables each of the eight
listener inputs in-1 to in-8 to
be enabled or disabled
without affecting any
parameters.
See section 5.4.4

‘SrC’

Enter Source Address

Allows hexadecimal fieldbus
device source address for
each of the eight listener
inputs in-1 to in-8 to be
entered.
See section 5.4.5

‘dSt’

Enter Destination Address

Allows hexadecimal fieldbus
device destination address for
each listener input in-1 to in-8
to be entered.
See section 5.4.6

‘ind’

Enter Index

Allows hexadecimal index for
specified fieldbus source
address to be entered for
each listener input  in-1 to in-
8.
See section 5.4.7

‘dP’

Decimal point position

Defines position of displayed
decimal point for each listener
input in-1 to in-8.
See section 5.4.8

‘bAr’

Configuration of bargraph

Defines the bargraphs
justification and the digital
display at which the bargraph
is zero and full scale for each
listener input in-1 to in-8.
See section 5.4.9

‘SCALE’

Scale numeric display

Applies zero offset and scale
factor to the numeric display
for each listener input in-1 to
in-8.
See section 5.4.10

‘CodE’

Access code for listener
configuration menu

Enters a four digit security access
code for configuration menu.  Default
code 0000 disables this function.
See section 5.4.11

tYPE’

Change from listener to node

Enables the instrument to be
conditioned as a fieldbus listener or a
fieldbus node.
See section 5.4.12

‘rESEt’

Reset to listener factory defaults

Returns the BA644DF-P listener to
factory defaults.
See section 5.4.13

Summary of Contents for BA644DF-P

Page 1: ...Issue 3 4th March 2014 BA644DF P PROFIBUS PA Field mounting 8 variable Fieldbus Indicator Issue 3 ...

Page 2: ...ers 5 4 3 Enter address display parameters 5 4 4 Enable selected input 5 4 5 Enter source address 5 4 6 Enter destination address 5 4 7 Enter Index 5 4 8 Decimal point position 5 4 9 Configuration of bargraph 5 4 10 Scale numeric display 5 4 11 Access code for listener configuration menu 5 4 12 Change from fieldbus listener to fieldbus node 5 4 13 Reset to listener factory defaults 6 Maintenance 6...

Page 3: ...re is an alternative version of the fieldbus display order code BA644DF F for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes installation configuration and use of the BA644DF P as a PROFIBUS PA listener and as a PROFIBUS PA node For additional node configuration information please refer to the BEKA PROFIBUS PA Display Fieldbus Interface Guide which is avail...

Page 4: ...l should be connected to the potential equalising network The BA644DF P enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries 4 2 Installation Procedure Fig 2 illustrates the instrument installation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the instrument on a flat surface and secure ...

Page 5: ...5 Fig 3 Dimensions and terminal connections ...

Page 6: ...ting the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button will enter the new address and the indicator will restart in the display mode after completing the initialisation sequence If the address is not changed operating the E button will return the display t...

Page 7: ...e BA644DF P listener are not known In the SCAn function pressing the P button causes the BA644DF P listener to search the fieldbus segment to which it is connected for all data sources The hexadecimal device addresses for each data source are displayed as shown in Fig 5 The and push buttons scroll the display through all the data sources on the segment showing the source and destination address fo...

Page 8: ...8 ...

Page 9: ...meters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 5 4 3 Enb Enable selected input Enables each of the eight listener inputs in 1 to in 8 to be enabled or disabled without affecting any parameters See section 5 4 4 SrC Enter Source Address Allows hexadecimal fieldbus device source...

Page 10: ... source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a listener input any previous allocation will be overwritten If the required process variable has an index above 5 i e it is not the first five bytes in the data string the required index should be ent...

Page 11: ...ay mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 5 4 9 Configuration of bargraph display bAr This function contains three sub functions that enable the bargraph justify its position and define the relationship between the bargraph and the instrument s numeric display Sub function b...

Page 12: ...revised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 5 4 12 Change from fieldbus listener to fieldbus node tYPE This function enables the BA644DF P to be conditioned as a fieldbus node or as a fieldbus listener To change the function of the instrument select tYPE in the listener configuration menu using...

Page 13: ...egments activated Display is initialising This is normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering the display mode 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA644DF P fails after it has been functioning correctly the table shown in section 6 1 may help to identify the cause o...

Page 14: ... new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 7 2 Tag plate The BA644DF P can be supplied with a blank or custom laser marked stainless steel plate secured by two screws to the front of the instrument enclosure This plate can accommodate 1 row of 9 alphanumeric characters 10mm high or 1 row of 11 alphanumeric c...

Reviews: