1.  DESCRIPTION

The BA644DF-P fieldbus indicator is a PROFIBUS
PA instrument that may be configured as a fieldbus
node or as a fieldbus listener. It can display up to
eight fieldbus process variables on a five digit LCD
and a 31 segment analogue bargraph.   The
instrument is bus powered so no additional power
supply is required and has PROFIBUS PA User
Organisation approval, certificate Z01505.

Fieldbus node configuration may be performed by
either a User PRM data download or by a DPV1
configurator, and if required, the instrument
address may be entered via the front panel push
buttons.

When configured as a fieldbus listener, the
BA644DF-P is not visible to the fieldbus host and
can only be configured using the push buttons on
the front of the instrument.

Housed in a robust IP66 glass reinforced polyester
(GRP) enclosure with a toughened glass window,
the BA644DF-P is surface mounting, or may be
pipe mounted using one of the accessory kits.

The instrument’s communication protocol is shown
on a label inside the terminal cover.  The ‘-P’ order
code suffix also indicates the protocol but is not
shown on the instrument identification label.
There is an alternative version of the fieldbus
display, order code BA644DF-F for use on
FOUNDATION™ fieldbus networks.

1.1

  

Documentation

This instruction manual describes installation,
configuration and use of the BA644DF-P as a
PROFIBUS PA listener and as a PROFIBUS PA
node.    For additional node configuration
information please refer to the 

BEKA PROFIBUS

PA Display – Fieldbus Interface Guide

 which is

available from the BEKA sales office, or may be
downloaded from www.beka.co.uk

2.  OPERATION

The BA644DF-P indicator can display up to eight
pre-configured PROFIBUS PA process variables
designated in-1 to in-8.   The operator can select
which variable is displayed using the 

and 

push buttons which scroll the display through the
eight inputs.   A numeric annunciator on the left
hand side of the display shows which of the eight
inputs is currently being displayed.

2.1  Error messages

‘no ConF’

No inputs have been
configured or are enabled.

‘no dAtA’

No data is being received
with the current configuration.

3.  SYSTEM DESIGN

The BA644DF-P PROFIBUS PA indicator is
powered and communicates via the fieldbus which
is connected to non-polarised terminals 1 and 2 as
shown in Fig 1.  The indicator may be connected to
any PROFIBUS PA segment that can supply an
additional 13mA at between 9 and 32V required to
power the instrument.

Fig 1   Typical PROFIBUS PA segment

Summary of Contents for BA644DF-P

Page 1: ...Issue 3 4th March 2014 BA644DF P PROFIBUS PA Field mounting 8 variable Fieldbus Indicator Issue 3 ...

Page 2: ...ers 5 4 3 Enter address display parameters 5 4 4 Enable selected input 5 4 5 Enter source address 5 4 6 Enter destination address 5 4 7 Enter Index 5 4 8 Decimal point position 5 4 9 Configuration of bargraph 5 4 10 Scale numeric display 5 4 11 Access code for listener configuration menu 5 4 12 Change from fieldbus listener to fieldbus node 5 4 13 Reset to listener factory defaults 6 Maintenance 6...

Page 3: ...re is an alternative version of the fieldbus display order code BA644DF F for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes installation configuration and use of the BA644DF P as a PROFIBUS PA listener and as a PROFIBUS PA node For additional node configuration information please refer to the BEKA PROFIBUS PA Display Fieldbus Interface Guide which is avail...

Page 4: ...l should be connected to the potential equalising network The BA644DF P enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries 4 2 Installation Procedure Fig 2 illustrates the instrument installation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the instrument on a flat surface and secure ...

Page 5: ...5 Fig 3 Dimensions and terminal connections ...

Page 6: ...ting the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button will enter the new address and the indicator will restart in the display mode after completing the initialisation sequence If the address is not changed operating the E button will return the display t...

Page 7: ...e BA644DF P listener are not known In the SCAn function pressing the P button causes the BA644DF P listener to search the fieldbus segment to which it is connected for all data sources The hexadecimal device addresses for each data source are displayed as shown in Fig 5 The and push buttons scroll the display through all the data sources on the segment showing the source and destination address fo...

Page 8: ...8 ...

Page 9: ...meters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 5 4 3 Enb Enable selected input Enables each of the eight listener inputs in 1 to in 8 to be enabled or disabled without affecting any parameters See section 5 4 4 SrC Enter Source Address Allows hexadecimal fieldbus device source...

Page 10: ... source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a listener input any previous allocation will be overwritten If the required process variable has an index above 5 i e it is not the first five bytes in the data string the required index should be ent...

Page 11: ...ay mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 5 4 9 Configuration of bargraph display bAr This function contains three sub functions that enable the bargraph justify its position and define the relationship between the bargraph and the instrument s numeric display Sub function b...

Page 12: ...revised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 5 4 12 Change from fieldbus listener to fieldbus node tYPE This function enables the BA644DF P to be conditioned as a fieldbus node or as a fieldbus listener To change the function of the instrument select tYPE in the listener configuration menu using...

Page 13: ...egments activated Display is initialising This is normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering the display mode 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA644DF P fails after it has been functioning correctly the table shown in section 6 1 may help to identify the cause o...

Page 14: ... new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 7 2 Tag plate The BA644DF P can be supplied with a blank or custom laser marked stainless steel plate secured by two screws to the front of the instrument enclosure This plate can accommodate 1 row of 9 alphanumeric characters 10mm high or 1 row of 11 alphanumeric c...

Reviews: