5.4 Description of listener menu functions

This section contains a detailed description of each
function in the listener configuration menu.  It
should be read in conjunction with Fig 6.

5.4.1  Scan fieldbus segment  ‘SCAn’

If the Device Addresses of a data source are not
known, the ‘SCAn’ function provides a simple way
to identify them. This function scans the fieldbus
segment to which the BA644DF-P listener is
connected and identifies all the data sources.  To
aid identification the value of the process variable
with a zero index i.e. the first five bytes in the data
string at the address may be pre-viewed.

The BA644DF-P listener only supports DS-33
formatted data (float) which is the usual
format for analogue process variables.   The
‘SCAn’ function will identify, irrespective of format,
all data sources on the segment whose destination
address is five bytes long.  When pre-viewed, non
DS-33 formatted data will produce a ‘no dAt’ error
message.

‘SCAn’ is the first function displayed when entering
the configuration menu, or it may be selected from
within the menu by operating the 

 or 

 button.

To scan the fieldbus segment to which the listener
is connected for all data sources press 

P

 which will

reveal the hexadecimal source address and
destination address of the first data source found
as shown in Fig 5.    If there is more than one data
source, operating the 

 or 

 button will scroll

though all of them.

If there are no data sources on the fieldbus
segment the BA644DF-P listener will display
‘noSrC’.

When the source and destination addresses of a
data source are displayed, to aid identification the
value of the process variable with a zero index i.e.
the first five bytes in the data string may be pre-
viewed by operating the 

P

 button.   If this confirms

that it is the required address, it may be allocated
to one of the eight BA644DF-P listener inputs in-1
to in-8.   To select the required listener input, press

P

 which will display the first input in-1.  Operating

the 

 or 

 button will scroll the display through

the other inputs.  When the required input is
displayed pressing 

E

 will allocate the selected data

source address to the selected input and return the
display to the source and destination addresses
from which another data source address may be
selected.  When a data source address is allocated
to a listener input any previous allocation will be
overwritten.

If the required process variable has an index
above 5  i.e.  it is not the first five bytes in the data
string, the required index should be entered via the
‘ind’ function in the Edit sub-menu which is
described in section5.4.7

5.4.2 List configured input parameters   ‘LiSt’

The ‘LiSt’ function enables the Source Address,
Destination Address and Index allocated to each
listener input to be viewed without danger of it
being accidentally changed.

The ‘LiSt’ function may be selected from within the
menu by operating 

 or 

 button. To enter the

function press 

P

 which will display the listener

input currently selected in the display mode, other
inputs may be selected using the 

 or 

 button.

Operating the 

P

 button will cause the following

parameters for the selected input to be displayed
sequentially:

           

Display                    Explanation

‘Enb :Y or N’

Input Enabled yes or no

‘SrC :00’

Source Address

‘dSt :00’

Destination Address

‘ind :00’ Index

The display then automatically returns to the
selected BA644DF-P listener input from where
another input may be selected.

If one of the eight BA644DF-P Listener’s inputs in-
1 to in-8 has not had a Source Address,
Destination Address and Index allocated to it, ‘LiSt’
will show both addresses as ‘FF’ and the index
‘ind’ as ‘00’.

5.4.3  Enter address & display parameters
          ‘Edit’

The ‘Edit’ sub-menu may be selected from within
the menu by operating 

 or 

 button. To enter the

function press 

P

 which will display the listener

input currently selected in the display mode, other
listener inputs may be selected using the 

 or 

button.  When the required input has been
selected operating the 

P

 button will enter the edit

sub-menu at ‘Enb’ for the selected input.

5.4.4  Enable selected input    ‘Enb’

‘Enb’ turns the listener input selected in the Edit
function on or off without affecting the conditioning.
To enter the function press 

P

 which will reveal

whether the selected input is ‘on’ or ‘oFF’.
Operating the 

 or 

 buttons will toggle between

the two conditions.  When set as required
operating the 

E

 button will enter the selection and

return to the ‘Enb’ prompt in the edit sub-menu.

Summary of Contents for BA644DF-P

Page 1: ...Issue 3 4th March 2014 BA644DF P PROFIBUS PA Field mounting 8 variable Fieldbus Indicator Issue 3 ...

Page 2: ...ers 5 4 3 Enter address display parameters 5 4 4 Enable selected input 5 4 5 Enter source address 5 4 6 Enter destination address 5 4 7 Enter Index 5 4 8 Decimal point position 5 4 9 Configuration of bargraph 5 4 10 Scale numeric display 5 4 11 Access code for listener configuration menu 5 4 12 Change from fieldbus listener to fieldbus node 5 4 13 Reset to listener factory defaults 6 Maintenance 6...

Page 3: ...re is an alternative version of the fieldbus display order code BA644DF F for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes installation configuration and use of the BA644DF P as a PROFIBUS PA listener and as a PROFIBUS PA node For additional node configuration information please refer to the BEKA PROFIBUS PA Display Fieldbus Interface Guide which is avail...

Page 4: ...l should be connected to the potential equalising network The BA644DF P enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries 4 2 Installation Procedure Fig 2 illustrates the instrument installation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the instrument on a flat surface and secure ...

Page 5: ...5 Fig 3 Dimensions and terminal connections ...

Page 6: ...ting the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button will enter the new address and the indicator will restart in the display mode after completing the initialisation sequence If the address is not changed operating the E button will return the display t...

Page 7: ...e BA644DF P listener are not known In the SCAn function pressing the P button causes the BA644DF P listener to search the fieldbus segment to which it is connected for all data sources The hexadecimal device addresses for each data source are displayed as shown in Fig 5 The and push buttons scroll the display through all the data sources on the segment showing the source and destination address fo...

Page 8: ...8 ...

Page 9: ...meters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 5 4 3 Enb Enable selected input Enables each of the eight listener inputs in 1 to in 8 to be enabled or disabled without affecting any parameters See section 5 4 4 SrC Enter Source Address Allows hexadecimal fieldbus device source...

Page 10: ... source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a listener input any previous allocation will be overwritten If the required process variable has an index above 5 i e it is not the first five bytes in the data string the required index should be ent...

Page 11: ...ay mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 5 4 9 Configuration of bargraph display bAr This function contains three sub functions that enable the bargraph justify its position and define the relationship between the bargraph and the instrument s numeric display Sub function b...

Page 12: ...revised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 5 4 12 Change from fieldbus listener to fieldbus node tYPE This function enables the BA644DF P to be conditioned as a fieldbus node or as a fieldbus listener To change the function of the instrument select tYPE in the listener configuration menu using...

Page 13: ...egments activated Display is initialising This is normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering the display mode 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA644DF P fails after it has been functioning correctly the table shown in section 6 1 may help to identify the cause o...

Page 14: ... new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 7 2 Tag plate The BA644DF P can be supplied with a blank or custom laser marked stainless steel plate secured by two screws to the front of the instrument enclosure This plate can accommodate 1 row of 9 alphanumeric characters 10mm high or 1 row of 11 alphanumeric c...

Reviews: