5.  CONFIGURATION

The BA644DF-P 8 variable PROFIBUS PA
indicator may be configured as a fieldbus node or
as a fieldbus listener.   When used as a fieldbus
node the indicator is configured via the fieldbus
host although the instrument address may be
entered via the front panel push buttons using the
menu shown in Fig 4.   For detailed node
conditioning information please refer to the 

BEKA

PROFIBUS PA Display – Fieldbus Interface Guide

which may be downloaded from the BEKA website
www.beka.co.uk

As a fieldbus listener, the BA644DF-P is not visible
to the fieldbus host and can only be configured via
the front panel push buttons using the menu
shown in Fig 6.

Throughout this manual the four BA644DF-P push
buttons are identified 

P  E

   

 

 and legends

displayed by the instrument are shown within
inverted commas  e.g. ‘CodE’ and ‘Enb’.

5.1  Configuration menus

The configuration menus are separated into two
sections, fieldbus node and fieldbus listener.   Both
contain the ‘tYPE’ function that enables transfer
between the two.   Unless otherwise requested
when ordered, all PROFIBUS PA BA644DF-P
instruments are supplied as a fieldbus node with
default configuration but can easily be reconfigured
on-site.

5.2 Node configuration menu

The node configuration menu is shown in Fig 4.
Access to the menu is obtained by operating the 

P

and 

E

 buttons simultaneously.  If the BA644DF-P

is not protected by an access code the first
parameter 'Addr’ will be displayed.  If the
instrument is protected by an access code, ‘CodE’
will be displayed first.  Pressing 

P

 will allow the

four digit security code to be entered digit by digit
using the 

 or 

 button to adjust the flashing digit

and 

P

 to move control to the next digit.  When the

correct code has been entered, pressing 

E

 will

cause the first parameter ‘Addr’ to be displayed.
If an incorrect code is entered, or no button is
pressed for ten seconds, the BA644DF-P will
automatically return to the display mode.

5.2.1 Enter fieldbus address      ‘Addr’

This function enables the fieldbus address of the
BA644DF-P to be entered via the push buttons.
Select ‘Addr’ in the node menu using the 

 or 

button and press 

P

 to enter the function.  This will

reveal the existing three digit decimal address with
the left hand digit flashing which may be changed
by operating the 

 or 

 button.   When set as

required operating the 

P

 button will transfer control

to the next digit that may be adjusted in the same
way.

When all digits are set as required operating the 

E

button will enter the new address and the indicator
will restart in the display mode after completing the
initialisation sequence.  If the address is not
changed, operating the 

E

 button will return the

display to the ‘Addr’ prompt in the node
configuration menu.

5.2.2  Access code for configuration menu
          ‘CodE’

Access to the node configuration menu may be
protected by a four digit security code which must
be entered to gain access.  New instruments are
supplied configured with the default code 0000
which disables this protection and allows
unrestricted access to the configuration menu.

To enter a new access code select ‘CodE’ in the
node configuration menu by operating the 

 or 

button.   To enter the function press 

P

 which will

reveal the current access code with one digit
flashing. The code may be changed using the 

 or

 button to adjust the flashing digit and the 

P

button to move control to the next digit.  When the
required code has been selected, press 

E

 to enter

the selection and return to the ‘CodE’ prompt in the
configuration menu.    The revised access code will
be activated when the transmitter is returned to the
display mode.
If the access code is lost please contact BEKA
associates.

5.2.3  Change from node to listener   ‘tYPE’

This function enables the instrument to be
changed from a fieldbus node to a fieldbus listener.
Select ‘tYPE’ in the node configuration menu using
the 

 or 

 button. To enter the function press 

P

which will show that the instrument is configured
as a fieldbus node, to change to a fieldbus listener
press the 

 or 

 button which will toggle the

display to ‘LStnr’   To prevent accidental  changes
this request must be confirmed by operating the 

P

button and entering  ‘5urE’.  The instrument will
display ‘0000’ with the first digit flashing, using the

 or 

 button set the flashing digit to ‘5’ and press

the 

P

 button to move control to the next digit which

should be set to ‘u’.  When the four letters of ‘5urE’
have been entered, operating the 

E

 button will

cause the instrument to restart as a fieldbus
listener in the display mode.

CAUTION

All the instrument’s node configuration
information will be lost when it is
changed from a fieldbus node to a
fieldbus listener.

Please refer to the quick set-up procedure in the

BEKA PROFIBUS PA Display – Fieldbus Interface
Guide

.

Summary of Contents for BA644DF-P

Page 1: ...Issue 3 4th March 2014 BA644DF P PROFIBUS PA Field mounting 8 variable Fieldbus Indicator Issue 3 ...

Page 2: ...ers 5 4 3 Enter address display parameters 5 4 4 Enable selected input 5 4 5 Enter source address 5 4 6 Enter destination address 5 4 7 Enter Index 5 4 8 Decimal point position 5 4 9 Configuration of bargraph 5 4 10 Scale numeric display 5 4 11 Access code for listener configuration menu 5 4 12 Change from fieldbus listener to fieldbus node 5 4 13 Reset to listener factory defaults 6 Maintenance 6...

Page 3: ...re is an alternative version of the fieldbus display order code BA644DF F for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes installation configuration and use of the BA644DF P as a PROFIBUS PA listener and as a PROFIBUS PA node For additional node configuration information please refer to the BEKA PROFIBUS PA Display Fieldbus Interface Guide which is avail...

Page 4: ...l should be connected to the potential equalising network The BA644DF P enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries 4 2 Installation Procedure Fig 2 illustrates the instrument installation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the instrument on a flat surface and secure ...

Page 5: ...5 Fig 3 Dimensions and terminal connections ...

Page 6: ...ting the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button will enter the new address and the indicator will restart in the display mode after completing the initialisation sequence If the address is not changed operating the E button will return the display t...

Page 7: ...e BA644DF P listener are not known In the SCAn function pressing the P button causes the BA644DF P listener to search the fieldbus segment to which it is connected for all data sources The hexadecimal device addresses for each data source are displayed as shown in Fig 5 The and push buttons scroll the display through all the data sources on the segment showing the source and destination address fo...

Page 8: ...8 ...

Page 9: ...meters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 5 4 3 Enb Enable selected input Enables each of the eight listener inputs in 1 to in 8 to be enabled or disabled without affecting any parameters See section 5 4 4 SrC Enter Source Address Allows hexadecimal fieldbus device source...

Page 10: ... source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a listener input any previous allocation will be overwritten If the required process variable has an index above 5 i e it is not the first five bytes in the data string the required index should be ent...

Page 11: ...ay mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 5 4 9 Configuration of bargraph display bAr This function contains three sub functions that enable the bargraph justify its position and define the relationship between the bargraph and the instrument s numeric display Sub function b...

Page 12: ...revised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 5 4 12 Change from fieldbus listener to fieldbus node tYPE This function enables the BA644DF P to be conditioned as a fieldbus node or as a fieldbus listener To change the function of the instrument select tYPE in the listener configuration menu using...

Page 13: ...egments activated Display is initialising This is normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering the display mode 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA644DF P fails after it has been functioning correctly the table shown in section 6 1 may help to identify the cause o...

Page 14: ... new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 7 2 Tag plate The BA644DF P can be supplied with a blank or custom laser marked stainless steel plate secured by two screws to the front of the instrument enclosure This plate can accommodate 1 row of 9 alphanumeric characters 10mm high or 1 row of 11 alphanumeric c...

Reviews: