EVVO 20000TLG23P~EVVO 33000TLG23P
EVVO 20000TLG23P~EVVO 33000TLG23P
49
50
On-Off Control
Users press ''Back'' button to enter ''1. Enter Setting'' interface, Press ''OK'' button to
enter main setting interface. Enter ''5. On-Off Control'' by pressing ''UP'' button or
''Down'' button. Press ''OK'' button and enter On-Off Control interface, press ''OK'' button
and enter ''Input Password'' Setting interface. Press ''OK'' button to set
passwords (default:0001), increase or decrease value though pressing ''Up'' button
or ''Down'' button, press ''OK'' button to next value
setting. ‘Error! Try again'' will be
displayed for wrong passwords. Press ''back'' button and rekey in the correct passwords.
It will enter into ''Power on Power off'' interface if the passwords is correct, then you
can select ''Power on'' or ''Power off'' by pressing ''Up'' button or ''Down'' button and
press ''OK'' button to finish the setting successfully. If you select ''Power
off’ ‘need to
set how many days you want the inverter to power off, increase or decrease value
though pressing ''Up'' button or ''Down'' button. After you set ''Power off'' successfully,
you need to contact manufacturer to supply passwords to re-power on this inverter.
Relay Command
Users press
“Back” button to enter “1. Enter Setting” interface, Press” OK“ button to enter
main setting interface.
Enter
“6. Relay Command” by pressing “Up” button or” down “button, press “OK ” button
and
enter “Relay Command setting “interface. Choose corresponded setting items by
pressing
“Up” button or “Down” button, then press “OK” button. “success” or “fail” is
displayed after setting.
Relay Command Definition:
Production
the relay switches whenever a connection to (or a disconnection from) the grid
occurs.
If the relay contractor is in normally open (close) mode, the contact will stay open
(or closed) until the inverter is connected to the grid; once the inverter connects to
the grid and starts to export power, the relay switches state and therefore closes (or
opens).
When the inverter disconnects from the grid, the relay contact returns to its
position of rest, namely open (or closed).
Alarm
The relay switches whenever there is an alarm on the inverter (Error). No
switching occurs when there is a Warning.
If the relay contractor is in normally open(close)mode, the contact will stay open
(or closed) until the inverter reports an error; once the inverter reports an error, the
relay switches state and therefore closes (or opens).The contact remains switched
from its rest condition until normal operation is restored.
Config Alarm
the relay switches whenever there is an alarm (Error) or a Warning, which have
been previously selected by the user through the PC. the contact will stay open (or
closed) until the inverter reports an error or a warning out of those selected from
the menu; once the inverter displays an error or a warning out of those selected, the
relay switches state and therefore closes (or opens) the contact. The relay remains
switched from its rest condition until the alarm or warning has disappeared.
Relay Disable
Control function is forbidden
Enable Set Country
Users press “Back” button to enter “1. Enter Setting” interface, Press “OK” button to enter
main setting interface. Enter
“7.Enable Set Country” by pressing “Up” button
or“Down”button, press “OK” button and enter “Input Password” Setting interface.
Press
“Back” button to set passwords (default: 0001), increase or decrease value though
pressing
“Up” button or “Down” button, press “OK” button to next value setting. “Error! Try
again” will be displayed for wrong passwords. Press “Back” button and rekey in the correct
passwords.
“success” will be displayed if setting successfully,
Attention: when inverter working for power generation over 24h, country setting is
forbidden, it can only be set after LCD setting (7. Enable Set Country). Key in passwords for
country setting through LCD (default: 0001), country setting can be set in 24h after keying in
the correct passwords, over 24h, set "7. Enable Set Country" first, then set "4. Set Country
Code" to change country code.
Set Address
Users press
“Back” button to enter “1. Enter setting” interface, Press” OK“ button to
enter main setting interface. Enter
“9. Set Address” by pressing “Up” button or” Down“
button. Press
“OK” button and enter setting interface “Success” or “fail” is displayed after
setting.
6
.
Relay Command
1. Production
2. Alarm
3. Config Alarm
4. Relay Disable