WT.050.200.001.UA.IM.0814
50-200 EVAPORATOR FOR CHLORINE
54
EVOQUA
W3T98237
Table 4.1 - Troubleshooting (Cont'd)
Symptom
Probable Cause
Corrective Action
Group 8
Water Coming Out of Overflow
Connection and/or Spilling Over
Tank Top Onto Floor.
Sight Glass in Water Level
Indicator is Full or Nearly Full.
Possible Additional Symptom:
Low Water Temperature Alarm**
(If Provided) and Panel Light
Activate.
High water level as a result of any
of the following conditions:
(a) Foreign material jamming sole-
noid valve open.
(b) Faulty solenoid valve.
(c) Automatic water refill circuit
failure or incorrect level probe
wiring.
(a) Clean solenoid valve.
(b) Replace valve.
(c) Replace faulty controls or
check wiring.
**Alarms will not activate if customer power fails.