50-200 EVAPORATOR FOR CHLORINE
WT.050.200.001.UA.IM.0814
51
EVOQUA
W3T98237
Table 4.1 - Troubleshooting (Cont'd)
Symptom
Probable Cause
Corrective Action
Group 4
Evaporator Pressure Relief
System Pressure Alarm**
Activates but Front Panel
Pressure Gauge Reads Between
30 and 140 PSI.
-OR-
Liquid Line Pressure Relief
System Alarm** Activates but
Liquid Line Pressure Gauge Reads
Between 30 and 140 PSI.
Rupture disc leaks.
Following Long-Term Shutdown
processdure in Section 3. Replace
disc.
**Alarms will not activate if customer power fails.