WT.025.000.001.UA.IM.0614
PAGE 7
CHLORINE HANDLING MANUAL
EVOQUA
W3T98244
Figure 10 – Standard Safety Relief Device
subsurface locations should leaks occur. Do not store or use
chlorine containers near other chemicals or gases.
WARNING: STORE CYLINDERS IN AN UPRIGHT POSITION.
TO AVOID SEVERE PERSONAL INJURY OR EQUIPMENT
DAMAGE, SUPPLY CYLINDERS MUST BE SECURED IN
SUCH A MANNER (E.G., CHAIN) AS TO PREVENT THEIR
BEING KNOCKED OVER. TON CONTAINERS MUST BE SE-
CURED IN SUCH A MANNER (E.G., CROCKS) TO PREVENT
THEIR ROLLING OUT OF PLACE.
Do not remove the protective cap or hood from cylinders or
ton containers until they are ready to be put in actual use.
Do not store containers in a heavily traveled area where
physical contact damage could occur.
It is essential that areas used to house chlorine containers or
equipment be continuously monitored for the presence of
chlorine in the air. This may be a requirement of applicable
laws and/or regulations.
When containers are moved from a storage area to an area
where they will be used, allow sufficient time to stabilize the
temperature, and therefore the pressure, of the container
and the chlorine before it is used.
The chlorine inventory depends to a large extent on local
availability. Consult with chlorine suppliers in the area; review
appropriate fire code requirements concerning storage of
oxidizing materials and other applicable laws and regulations.
When planning space for stored containers, sufficient space
must be allowed for empty containers. The best way to
determine the amount of chlorine remaining in a container
is to weigh the container continuously on a scale. This also
makes it possible to record the amount of chlorine used.
Portable or dormant scales in beam, dial, or digital types
and with varying platform sizes are available.
WARNING: ALWAYS REMOVE WHEELS AND AXLES OF
PORTABLE SCALES SO THAT THE SCALE CANNOT MOVE
WHEN CYLINDERS ARE ON THE PLATFORM.
Preferably, scales for cylinders should be installed with
their platform flush with the floor to eliminate the neces-
sity of lifting the cylinders. Some low profile scales such as
the Wallace & Tiernan
®
Cylinder Scale are low enough that
cylinders can be placed on the scale without lifting. Others
are installed with ramps. If scales are pit mounted, a trapped
drain should be provided.
Scales for ton containers are usually installed above the floor,
since ton containers are usually handled by overhead con-
veyor. Many of these scales do not have platforms since the
ton containers are usually supported by cradles or trunnions.
Special high-capacity scales are provided at some installa-
tions using tank cars. These scales are usually pit mounted
below the railroad siding with the dial or digital unit housed
above ground beside the track.
Some of the dial or digital scales are equipped with loss-of-
weight recording systems providing a permanent record of
chlorine usage.
3.6 HANDLING CONTAINERS
Always handle chlorine containers with utmost care. To
prevent injury or damage, do not drop chlorine containers
and do not permit containers to strike each other or other
objects. To prevent damage to the valve, valve protecting
caps or hoods must always be in place when containers are
moved.
Handle cylinders with a simple two-wheel hand truck of the
barrel pattern. Hand trucks should be well balanced and
equipped with chains or clamps to prevent the cylinders
from falling off the truck.
Summary of Contents for Wallace&Tiernan 50-200 Series
Page 1: ...Series 50 200 Evaporator For Chlorine BOOK NO WT 050 200 001 UA IM 0814 W3T198237 ...
Page 2: ...SERIES 50 200 EVAPORATOR FOR CHLORINE BOOK NO WT 050 200 001 UA IM 0814 W3T198237 ...
Page 15: ...WT 050 200 001 UA IM 0814 50 200 EVAPORATOR FOR CHLORINE 4 EVOQUA W3T98237 ...
Page 75: ...WT 050 200 001 UA IM 0814 50 200 EVAPORATOR FOR CHLORINE 64 EVOQUA W3T98237 ...
Page 95: ...CHLORINE HANDLING MANUAL Cl2 BOOK NO WT 025 000 001 UA IM 0614 W3T98244 ...