4.4 Water Loop Connection 

Pay attention to the below matters when the water pipe is connected. 

 

Try to reduce the resistance to the water from the piping. 

 

The piping must be clear and free from dirt and blockage. A water leakage test must be carried out to ensure 

that there is no water leaking before the installation can be made. 

 

The pipe must be tested by pressure separately. DO NOT test it together with the unit. 

 

There must be an expansion tank on the top point of the water loop, and the water level inside the tank 

must be at least 0.5meters higher than the top point of the water loop. 

 

The flow switch is installed inside of the heat pump, check to ensure that the wiring and action of the switch 

is normal and controlled by the controller. 

 

Try to avoid any air from being trapped inside the water pipe, there must be an air vent on the top point of 

the water loop. 

 

There must be a thermometer and pressure meter at the water inlet and outlet for easy inspection during 

running. 

4.5 Electrical Connection 

 

Open the front panel and open the power supply access. 

 

The power supply must go through the wire access and be connected to the power supply terminals in the 

controlling box. Then connect the 3-signal wire plugs of the wire controller and main controller. 

 

If an external water pump is required, please insert the power supply wire into the wire access and connect 

it to the water pump terminals. 

 

If an additional auxiliary heater is needed to be controlled by the heat pump controller, the relay (or power) 

of the aux-heater must be connected to the relevant output of the controller. 

 

4.6 Initial Start-up of the Unit 

INSPECTION BEFORE TRIAL RUNNING 

 

Check the indoor unit, make sure that the pipe connection is done correctly, and the relevant valves are open. 

 

Check the water loop to ensure that the water inside of the expansion tank is filled to an appropriate level, and 

the water supply is working, and the water loop is full of water and free of trapped air. Make sure there is good 

insulation for the water pipe. 

 

Check the electrical wiring. Make sure that the power voltage is normal, the screws are fastened, the wiring is 

made in line with the diagram and that the earthing is connected. 

 

Check that the heat pump includes all the screws and components, and that they are in good order. When 

powering the unit on, review the indicator on the controller to see if there is any indication of failure. The gas 

gauge can be connected to the check valve to see the high pressure (or low pressure) of the system during trial 

running. 

TRIAL RUNNING 

 

Start the heat pump by pressing the ‘POWER’ button key on the controller. Check whether the water pump is 

running, if it runs normally there will be 0.2MPa on the water pressure meter. 

 

When the water pump has ran for a minute, the compressor will start. Listen for any strange sounds from the 

compressor, if an abnormal sound occurs please stop the unit and check the compressor. If the compressor runs 

well please look for the pressure meter of the refrigerant. 

 

Check whether the power input and running current is in line with the manual. If not please stop and check. 

 

Adjust the valved on the water loop to make sure that the hot (cool) water supply to each door is good and 

meets the requirements of heating (or cooling). 

 

Review whether the outlet water temperature is stable. 

 

The parameters of the controller are set by the factory, the user cannot change these themselves. 

Summary of Contents for EVO FLEX 10

Page 1: ......

Page 2: ..._______________________________________________________________ 10 5 2 4 Fast Heating _____________________________________________________________________________ 10 5 2 5 Timer Setting _____________...

Page 3: ...x Series can adjust the output capacity automatically and control the room temperature accurately The Evo Flex Series is ideal for domestic hot water and space heating and cooling Latest DC invert hea...

Page 4: ...3 Evo Flex Manual 2 Unit Specifications 2 1 Unit Structure Evo Flex 10 Evo Flex 17 25...

Page 5: ...pressor Quantity 1 1 1 Compressor Model Rotary Rotary Rotary Fan Quantity 1 2 2 Fan Power Input W 75 75 X 2 150 X 2 Fan Rotate Speed RPM 850 850 900 Noise dB A 54 58 62 Water Pump Input kW 0 18 0 5 0...

Page 6: ...5 Evo Flex Manual 2 3 Dimensions Evo Flex 10 Evo Flex 17 Evo Flex 25...

Page 7: ...t pump is installed on a strong and stable platform A circuit breaker must be installed for the unit Use supply wires suitable for 75 C Caution Single wall heat exchanger not suitable for potable wate...

Page 8: ...able to support the weight of a heavy unit such as a terrace roof the ground and any other places deemed suitable The location must have good ventilation The location must be free from heat radiation...

Page 9: ...itial Start up of the Unit INSPECTION BEFORE TRIAL RUNNING Check the indoor unit make sure that the pipe connection is done correctly and the relevant valves are open Check the water loop to ensure th...

Page 10: ...presents enabled 6 Setup key Click this key to check the unit status time factory parameters temperature curve timer setting and mute setting 7 Fault icon This icon will flash when there is an error o...

Page 11: ...t temperature to be set a pop up keyboard will appear 3 Pressing 3 will allow the target temperature of cooling mode to be set through the keyboard When the target temperature is being set the followi...

Page 12: ...Interface Key Name Key Function 1 Status Key Click this key to get into the status interface 2 Clock Key Click this key to set the operational time function 3 Mute Key Click to turn on off silent func...

Page 13: ...g the fault records it will ask for a code The password will be according to the display date For example if the display date is 12 11 2016 then the password is 12 5 2 9 Colour Display Calibration Kee...

Page 14: ...erloaded Check whether the system of the compressor is running normally Communication Fault E08 Communication failure between wire controller and mainboard Check the wire connection between remote wir...

Page 15: ...on Fault DSP F11 DSP and Inverter board communication failure Check the communication connection Communication Fault Inverter Board F12 Communication failure between inverter board and main board Chec...

Page 16: ...eakage and recharge freon Block on filter or capillary Replace filter or capillary Lack of water flow Clean the water filter and discharge the air in water loop Compressor do not run Power supply fail...

Page 17: ...ral Valve 12 Drain Valve 5 Three way Valve 13 Non return valve 6 Y type Filter 14 Water Pump 7 Safety Valve 15 Fan Coil 8 Expansion Tank Installation Request 1 The Factory only offers one main unit 1...

Page 18: ...the handle A can return close when the system is full of water Automatic filled water valve needs periodic cleaning When you must close the tap unscrew the plug D remove the inside filter net Reassem...

Page 19: ...2 x 6mm2 6mm2 40A 32 40A 2 x 10mm2 10mm2 63A 40 63A 2 x 16mm2 16mm2 80A 63 75A 2 x 25mm2 25mm2 100A 75 101A 2 x 25mm2 25mm2 125A 101 123A 2 x 35mm2 35mm2 160A 123 148A 2 x 50mm2 50mm2 225A 148 186A 2...

Page 20: ...19 Evo Flex Manual 7 3 Controller Interface Drawing...

Page 21: ...m exhaust temperature input 20 AI04 Reserved 21 AI05 System suction temperature input 22 AI06 System coil temperature input 23 AI07 Ambient temperature input 24 AI08 Water tank temperature input 25 AI...

Page 22: ...rvice agents Please contact EvoHeat tech support on 1300 859 933 for your local service agent details Should I check my unit regularly We recommend you check your unit regularly to avoid potential iss...

Page 23: ...damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site b provide a copy of your receip...

Reviews: