Evo Flex Manual 

6.3 Troubleshooting Table 

Failure 

Possible Causes for the Failure 

Solutions 

Heat pump cannot be 

started 

Wrong power supply 

Shut off the power and check power supply 

Power supply cable loose 

Check power cable and make right 

connection 

Circuit breaker open 

Check for the cause and replace the fuse or 

circuit breaker 

Water pump is running 

with high noise or without 

heater 

Lack of water in the piping 

Check the water supply and charge water to 

the piping 

Too much air in the water loop 

Discharge the air in the water loop 

Water valves closed 

Open the valves in the water loop 

Dirt and blockage on the water filter 

Clean the water filter 

Heat pump capacity is low, 

compressor does not stop 

Lack of refrigerant 

Check for the gas leakage and recharge the 

refrigerant 

Bad insulation on water pipe 

Make good insulation on water pipe 

Low heat exchange rate on air side 

exchanger 

Clean the air side heat exchanger 

Lack of water flow 

Clean the water filter 

High compressor exhaust 

Too much refrigerant 

Discharge the redundant gas 

Low heat exchange rate on air side 

exchanger 

Clean the air side heat exchanger 

Low pressure problem of 

the system 

Lack of gas 

Check the gas leakage and recharge freon 

Block on filter or capillary 

Replace filter or capillary 

Lack of water flow 

Clean the water filter and discharge the air in 

water loop 

Compressor do not run 

Power supply failure 

Check off the power supply 

Compressor contactor broken 

Replace compressor contractor 

Power cable loose 

Tighten the power cable 

Protection on compressor 

Check the compressor exhaust temp 

Wrong setting on return water temp 

Reset the return water temp 

Lack of water flow 

Clean the water filter and discharge the air in 

water loop 

High noise of compressor 

Liquid refrigerant goes into compressor 

Bad evaporation, check the cause for bad 

evaporation and fix 

Compressor failure 

Use new compressor 

Fan do not run 

Failure on fan relay 

Replace the fan relay 

Fan motor broken 

Replace fan motor 

The compressor runs but 

heat pump has no heating 

or cooling capacity 

No gas in the heat pump 

Check system leakage and recharge 

refrigerant 

Heat exchanger broken 

Find out the cause and replace the heat 

exchanger 

Compressor failure 

Replace compressor 

Low outlet water 

temperature 

Low water flow rate 

Clean the water filter and discharge the air in 

water loop 

Low setting for the desired water temp 

Reset the desired water temperature 

Low water flow protection  Lack of water in the system 

Clean the water filter and discharge the air in 

water loop 

Failure on flow switch 

Replace the flow switch 

 

 

 

Summary of Contents for EVO FLEX 10

Page 1: ......

Page 2: ..._______________________________________________________________ 10 5 2 4 Fast Heating _____________________________________________________________________________ 10 5 2 5 Timer Setting _____________...

Page 3: ...x Series can adjust the output capacity automatically and control the room temperature accurately The Evo Flex Series is ideal for domestic hot water and space heating and cooling Latest DC invert hea...

Page 4: ...3 Evo Flex Manual 2 Unit Specifications 2 1 Unit Structure Evo Flex 10 Evo Flex 17 25...

Page 5: ...pressor Quantity 1 1 1 Compressor Model Rotary Rotary Rotary Fan Quantity 1 2 2 Fan Power Input W 75 75 X 2 150 X 2 Fan Rotate Speed RPM 850 850 900 Noise dB A 54 58 62 Water Pump Input kW 0 18 0 5 0...

Page 6: ...5 Evo Flex Manual 2 3 Dimensions Evo Flex 10 Evo Flex 17 Evo Flex 25...

Page 7: ...t pump is installed on a strong and stable platform A circuit breaker must be installed for the unit Use supply wires suitable for 75 C Caution Single wall heat exchanger not suitable for potable wate...

Page 8: ...able to support the weight of a heavy unit such as a terrace roof the ground and any other places deemed suitable The location must have good ventilation The location must be free from heat radiation...

Page 9: ...itial Start up of the Unit INSPECTION BEFORE TRIAL RUNNING Check the indoor unit make sure that the pipe connection is done correctly and the relevant valves are open Check the water loop to ensure th...

Page 10: ...presents enabled 6 Setup key Click this key to check the unit status time factory parameters temperature curve timer setting and mute setting 7 Fault icon This icon will flash when there is an error o...

Page 11: ...t temperature to be set a pop up keyboard will appear 3 Pressing 3 will allow the target temperature of cooling mode to be set through the keyboard When the target temperature is being set the followi...

Page 12: ...Interface Key Name Key Function 1 Status Key Click this key to get into the status interface 2 Clock Key Click this key to set the operational time function 3 Mute Key Click to turn on off silent func...

Page 13: ...g the fault records it will ask for a code The password will be according to the display date For example if the display date is 12 11 2016 then the password is 12 5 2 9 Colour Display Calibration Kee...

Page 14: ...erloaded Check whether the system of the compressor is running normally Communication Fault E08 Communication failure between wire controller and mainboard Check the wire connection between remote wir...

Page 15: ...on Fault DSP F11 DSP and Inverter board communication failure Check the communication connection Communication Fault Inverter Board F12 Communication failure between inverter board and main board Chec...

Page 16: ...eakage and recharge freon Block on filter or capillary Replace filter or capillary Lack of water flow Clean the water filter and discharge the air in water loop Compressor do not run Power supply fail...

Page 17: ...ral Valve 12 Drain Valve 5 Three way Valve 13 Non return valve 6 Y type Filter 14 Water Pump 7 Safety Valve 15 Fan Coil 8 Expansion Tank Installation Request 1 The Factory only offers one main unit 1...

Page 18: ...the handle A can return close when the system is full of water Automatic filled water valve needs periodic cleaning When you must close the tap unscrew the plug D remove the inside filter net Reassem...

Page 19: ...2 x 6mm2 6mm2 40A 32 40A 2 x 10mm2 10mm2 63A 40 63A 2 x 16mm2 16mm2 80A 63 75A 2 x 25mm2 25mm2 100A 75 101A 2 x 25mm2 25mm2 125A 101 123A 2 x 35mm2 35mm2 160A 123 148A 2 x 50mm2 50mm2 225A 148 186A 2...

Page 20: ...19 Evo Flex Manual 7 3 Controller Interface Drawing...

Page 21: ...m exhaust temperature input 20 AI04 Reserved 21 AI05 System suction temperature input 22 AI06 System coil temperature input 23 AI07 Ambient temperature input 24 AI08 Water tank temperature input 25 AI...

Page 22: ...rvice agents Please contact EvoHeat tech support on 1300 859 933 for your local service agent details Should I check my unit regularly We recommend you check your unit regularly to avoid potential iss...

Page 23: ...damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site b provide a copy of your receip...

Reviews: