background image

 

 

20 

Evo Flex Manual 

No. 

Sign 

Meaning 

01 

RO 01 

Compressor (output 220-230VAC) 

02 

RO 02 

Water Pump (output 220-230VAC) 

03 

RO 03 

4-way valve (output 220-230VAC) 

04 

RO 04 

Fan (output 220-230VAC) 

05 

RO 05 

Reserved 

06 

RO 06 

Anti-freezing heater (output 220-230VAC) 

07 

RO 07 

Crankshaft Heater (output 220-230VAC) 

08 

RO 08 

Spray Valve (output 220-230VAC) 

09 

RO 09 

Electric Auxiliary Heater (output 220-230VAC) 

10 

RO 10 

Reserved 

12 

RO 11 

Alarm (output 220-230VAC) 

12 

RO 12 

Hot Water Pump 

13 

RO 13 

Electromagnetic three-way valve 

14 

RO 14~RO18 

Reserved 

15 

AC-L 

Live Wire (output 220-230VAC) 

16 

AC-N 

Neutral Wire (output 220-230VAC) 

17 

AI01 

Water Inlet Temperature (input) 

18 

AI02 

Water output temperature (input) 

19 

AI03 

System exhaust temperature (input) 

20 

AI04 

Reserved 

21 

AI05 

System suction temperature (input) 

22 

AI06 

System coil temperature (input) 

23 

AI07 

Ambient temperature (input) 

24 

AI08 

Water tank temperature (input) 

25 

AI09-AI20 

Reserved 

26 

AI21 

Suction pressure input 

27 

AI22 

Exhaust pressure input 

28 

DI01 

System high pressure (input) 

29 

DI02 

System low pressure (input) 

30 

DI03 

Water flow switch (input) 

31 

DI04 

Emergency switch (input) 

32 

DI05 

Mode switch (input) 

33 

DI06 

Master-slave machine switch (input) 

34 

DI07 

Electric heating overload protection switch (input) 

35 

485_A1 

Frequency Conversion Board Communications 

36 

485_B1 

Frequency Conversion Board Communications 

37 

485_A2 

Communicate with wire controller and DC fan module 

38 

485_B2 

Communicate with wire controller and DC fan module 

39 

485_A3 

Reserved 

40 

485_B3 

Reserved 

41 

12V 

12V (output) 

42 

5V 

5V (output) 

43 

CN1 

Electronic expansion valve 

44 

CN2-CN4 

Reserved 

 

 

 

 

 

 

Summary of Contents for EVO FLEX 10

Page 1: ......

Page 2: ..._______________________________________________________________ 10 5 2 4 Fast Heating _____________________________________________________________________________ 10 5 2 5 Timer Setting _____________...

Page 3: ...x Series can adjust the output capacity automatically and control the room temperature accurately The Evo Flex Series is ideal for domestic hot water and space heating and cooling Latest DC invert hea...

Page 4: ...3 Evo Flex Manual 2 Unit Specifications 2 1 Unit Structure Evo Flex 10 Evo Flex 17 25...

Page 5: ...pressor Quantity 1 1 1 Compressor Model Rotary Rotary Rotary Fan Quantity 1 2 2 Fan Power Input W 75 75 X 2 150 X 2 Fan Rotate Speed RPM 850 850 900 Noise dB A 54 58 62 Water Pump Input kW 0 18 0 5 0...

Page 6: ...5 Evo Flex Manual 2 3 Dimensions Evo Flex 10 Evo Flex 17 Evo Flex 25...

Page 7: ...t pump is installed on a strong and stable platform A circuit breaker must be installed for the unit Use supply wires suitable for 75 C Caution Single wall heat exchanger not suitable for potable wate...

Page 8: ...able to support the weight of a heavy unit such as a terrace roof the ground and any other places deemed suitable The location must have good ventilation The location must be free from heat radiation...

Page 9: ...itial Start up of the Unit INSPECTION BEFORE TRIAL RUNNING Check the indoor unit make sure that the pipe connection is done correctly and the relevant valves are open Check the water loop to ensure th...

Page 10: ...presents enabled 6 Setup key Click this key to check the unit status time factory parameters temperature curve timer setting and mute setting 7 Fault icon This icon will flash when there is an error o...

Page 11: ...t temperature to be set a pop up keyboard will appear 3 Pressing 3 will allow the target temperature of cooling mode to be set through the keyboard When the target temperature is being set the followi...

Page 12: ...Interface Key Name Key Function 1 Status Key Click this key to get into the status interface 2 Clock Key Click this key to set the operational time function 3 Mute Key Click to turn on off silent func...

Page 13: ...g the fault records it will ask for a code The password will be according to the display date For example if the display date is 12 11 2016 then the password is 12 5 2 9 Colour Display Calibration Kee...

Page 14: ...erloaded Check whether the system of the compressor is running normally Communication Fault E08 Communication failure between wire controller and mainboard Check the wire connection between remote wir...

Page 15: ...on Fault DSP F11 DSP and Inverter board communication failure Check the communication connection Communication Fault Inverter Board F12 Communication failure between inverter board and main board Chec...

Page 16: ...eakage and recharge freon Block on filter or capillary Replace filter or capillary Lack of water flow Clean the water filter and discharge the air in water loop Compressor do not run Power supply fail...

Page 17: ...ral Valve 12 Drain Valve 5 Three way Valve 13 Non return valve 6 Y type Filter 14 Water Pump 7 Safety Valve 15 Fan Coil 8 Expansion Tank Installation Request 1 The Factory only offers one main unit 1...

Page 18: ...the handle A can return close when the system is full of water Automatic filled water valve needs periodic cleaning When you must close the tap unscrew the plug D remove the inside filter net Reassem...

Page 19: ...2 x 6mm2 6mm2 40A 32 40A 2 x 10mm2 10mm2 63A 40 63A 2 x 16mm2 16mm2 80A 63 75A 2 x 25mm2 25mm2 100A 75 101A 2 x 25mm2 25mm2 125A 101 123A 2 x 35mm2 35mm2 160A 123 148A 2 x 50mm2 50mm2 225A 148 186A 2...

Page 20: ...19 Evo Flex Manual 7 3 Controller Interface Drawing...

Page 21: ...m exhaust temperature input 20 AI04 Reserved 21 AI05 System suction temperature input 22 AI06 System coil temperature input 23 AI07 Ambient temperature input 24 AI08 Water tank temperature input 25 AI...

Page 22: ...rvice agents Please contact EvoHeat tech support on 1300 859 933 for your local service agent details Should I check my unit regularly We recommend you check your unit regularly to avoid potential iss...

Page 23: ...damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site b provide a copy of your receip...

Reviews: