background image

E2632

Rev 17.05.2021

Installation guidelines

There are no precise rules or standards to follow when installing gas detectors. The
following points must be taken into account:

Application (air quality control or leakage detection.)

Properties of the space under investigation (room geometry, direction, and
velocity of airflows, etc.),

Detected gas (relative density to air, temperature, whether the gas is flammable,
or toxiс, or oxygen displacing),

The device should be accessible for maintenance and repair.

The aforementioned conditions above will affect the coverage area of the device. However,
the coverage area for a detector is usually between 2.5 to 5 meters radius.

For early leakage detection install the sensor as close as possible to the potential leakage
sources (flanges, valves, pressure reducers, pumps, etc.), taking into consideration other
points listed above.

For general area monitoring without definite leakage sources, the detector should be
distributed evenly in the room.

Do not locate the detector close to ventilation openings and strong air currents. Avoid the
areas without air circulation (corners, niches) as well.

For personal safety control, the detectors are installed in the breathing zone (at the height
of the head of people or animals). The recommended sensor position is vertical, pointing
downwards.

6

Summary of Contents for E2632

Page 1: ...Two Channel Gas Detector E2632 User Manual...

Page 2: ...nts 5 Operating conditions 5 Installation guidelines 6 Mounting dimensions 7 Connections 8 Operation 9 Sensor probe handling 10 The electrochemical gas sensor replacement procedures 10 Maintenance 11...

Page 3: ...ioxide SO2 0 10 ppm 0 100 ppm Electrochemical 2 years 30 sec 6 months Ammonia NH3 0 100 ppm 0 500 ppm Electrochemical 2 years 50 sec 6 months Methane CH4 0 100 LEL Metal oxide semiconductor 5 years 60...

Page 4: ...max 5 A 30 VDC 250 VAC Alarm signaling Blinking LEDs buzzers 85 dB LEDs Green red operation fault red gas alarm Enclosure Grey ABS wall mount protection class IP65 Dimensions H123 W201 D55 mm Output c...

Page 5: ...components directly as they are sensitive to static electricity Connection diagrams can be found in the connections section The device might not perform correctly or be damaged if the wrong power sup...

Page 6: ...e area of the device However the coverage area for a detector is usually between 2 5 to 5 meters radius For early leakage detection install the sensor as close as possible to the potential leakage sou...

Page 7: ...E2632 Rev 17 05 2021 Mounting dimensions 7...

Page 8: ...of the external devices to each sensor Connect the power terminals N and L to the 24 V AC DC source if you are using detector version 24 or to 230 V AC mains if you are using detector version 230 see...

Page 9: ...the sensor to stabilize For stable operating it is recommended to keep the detector powered constantly except for periods of maintenance and calibration replacement etc Operation During the first ca 6...

Page 10: ...l launch blinking and beeping stops as soon as the key is withdrawn Sensor probe handling The sensor probes of all types are equipped with a hydrophobic microporous PTFE filter to protect the sensor f...

Page 11: ...fore delivery Provided that the sensor is used under moderate conditions field recalibration is recommended every few months The calibration intervals are stated in the gases table Please contact your...

Page 12: ...nufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manufa...

Reviews: