background image

 

 

 

 

Figure 5 

 

8.  The product water tubing/piping and associated fittings connecting the RO product outlet to 

the equipment being serviced should be food grade material that meets NSF Standard 51 or 
61  with  a  minimum  pressure  rating  of  75  PSI.  The  size  of  the  product  water  tubing/piping 
should be ½” ID minimum. Distances of 100 feet or greater from the RO to the equipment 
being  serviced  should  be  ¾”  ID  minimum.  Connect  the  appropriate  size  and  type  of 
tubing/piping and associated fittings to the RO product outlet on the MRS-200 system and 
route the lines to the equipment being serviced (i.e.; espresso, coffee, etc.). 

 

Note:

 The product water will react with most metal piping, creating a corrosive condition, in 

addition  to  imparting  an objectionable  taste.  Plastic  pipe  or  reinforced tubing  are generally 
very good choices for RO water distribution materials. 

 
9.  Locate the RO waste connection. Two  waste flow control assemblies have been provided. 

Based on the incoming water quality, select one of the following:

 

 

a. 

Systems  operating  on  hard  water  (>10  grains)  – 

Locate  the  flow  control  insert  (red 

plastic  cylinder  in  small  parts  kit).  Press  this  insert  into  the  red  ¼”  OD  tubing  (Fig.  6). 
Attach the end of the tubing with the flow control insert into the 3/8” stem x ¼” OD tube 
reducing fitting installed in the RO waste connection (Fig. 8). Route the other end of the 
tubing to a drain nearby, securing it 

permanently.

 Allow an air gap at the drain, following 

any applicable local codes. 

 
b. 

Systems operating on soft water (<10 grains) – 

Locate the capillary tubing assembly 

in the small parts kit. Insert the capillary tubing assembly into the red ¼” OD tubing (Fig. 
7). 

Do not shorten the capillary tubing at this time.

 Attach the end of the tubing with 

the capillary tubing assembly end fitting into the 3/8” stem x ¼” OD tube reducing fitting 
installed in the RO waste connection (Fig. 8). Route the other end of the tubing to a drain 
nearby,  securing  it 

temporarily

.  Allow  an  air  gap  at the  drain, following  any  applicable 

local  codes.  During  start-up,  refer  to  the  section  titled  “Adjusting  the  Recovery”  for 
instructions. 

Booster pump 
location shown is 
for reference only. 
See Figure 4 for 
actual location. 

INLET SUPPLY VALVE

BOOSTER

PUMP

INLET
3/8" OD TUBE CONNECTION

TO
DRAIN

(OPTIONAL)

1/2" NPT FEMALE THREADED

TO EQUIPMENT

PRODUCT WATER

CONNECTION

OUTLET

BY-PASS VALVE

Summary of Contents for MRS-200

Page 1: ...1 Cat No EV311117 Rev B 11 6 03 DCO 7060 MODEL MRS 200 Reverse Osmosis Mineral Reduction System Installation and Start up Guide...

Page 2: ...Installation 4 Cartridge Installation and Activation 10 Start Up and Blend Adjustment 10 Adjusting the Recovery 12 Operation 14 Maintenance 14 Performance Monitoring 16 TDS Measurement 16 Performance...

Page 3: ...hlorine An activated carbon filter has been provided with this system to protect the reverse osmosis membrane from chlorine attack Influent chlorine should not exceed 3 mg L The MRS 200 System consist...

Page 4: ...nd permit access for maintenance The system will weigh approximately 175 pounds when the storage tank is full 4 ____ Does the inlet water supply meet the requirements listed below 1 A minimum of 1 0 G...

Page 5: ...nts Place the main unit on the shelf positioning the cartridge heads directly over the cutout area Insert a cable tie into one of the holes in the baseplate and through the wire slats in the shelf mak...

Page 6: ...A MP S 2 INS E RT E LB OW FULLY 3 S LIDE LOCK ING CLIP UP TO S E CURE 1 S LIDE LOCK ING CLIP DOW N Figure 3 4 Water supplies with a dynamic operating pressure of 50 PSI or less require the use of the...

Page 7: ...UMP 10 NUT 8 1 2 X 1 SPACER 4 10 X 1 1 2 SCREW 8 10 WASHER 16 MOUNTING PLATE Figure 4 5 Refer to Figure 5 for a sample general arrangement Use this as a guideline for determining valve location tubing...

Page 8: ...ow control insert red plastic cylinder in small parts kit Press this insert into the red OD tubing Fig 6 Attach the end of the tubing with the flow control insert into the 3 8 stem x OD tube reducing...

Page 9: ...lt receptacle at this time Figure 9 Figure 7 Figure 8 INLET WATER SUPPLY 50 PSIG MAX TO 120 VAC OUTLET A B C SOLENOID VALVE 1 5 2 4 3 IN A B C TO 120 VAC OUTLET SOLENOID VALVE IN COVER REMOVED 3 4 2 5...

Page 10: ...ative solution from the RO cartridge and should not be consumed 6 If you are utilizing the capillary tubing assembly refer to the section titled Adjusting the Recovery for instructions Return to this...

Page 11: ...to contain a range of TDS greater than what an RO system normally produces In those cases a filtered water blend valve has been provided to blend in filtered not RO treated water to attain a specific...

Page 12: ...product flow with a 1000 ml graduated cylinder Don t worry if the flow is slightly more or less than what is specified 2 Determine the appropriate concentrate flow for your system and the desired rec...

Page 13: ...480 70 520 80 554 10 00 50 408 60 450 70 489 80 521 12 00 50 363 60 402 70 437 80 467 14 00 50 330 60 366 70 399 80 427 16 00 50 307 60 342 70 371 80 397 18 00 50 292 60 326 70 352 80 377 20 00 50 28...

Page 14: ...or 6 000 12 000 18 000 or 24 000 gallons d Calendar scale is jumper selectable for 6 months or 12 months Monitor operation a Active green light blinks every two seconds during any minimum water flow c...

Page 15: ...s or until the water is clear 10 Close the TO flush valve 11 Connect the 24 VAC Transformer from the 115 Volt receptacle Every 6 12 months Sanitize the storage tank 1 Refer to Start up section steps 1...

Page 16: ...and a graduated cylinder or calibrated measuring cup The drain water flow rate can be measured from the end of the red tubing in a similar manner Inlet water flow Outlet Product Water Flow Drain Wate...

Page 17: ...has removed 92 of the dissolved solids from the inlet water 6 The RO cartridge should be changed every 1 to 1 1 2 years or when the percent reduction falls below 90 A form has been provided below to r...

Page 18: ...valve as required to attain specified water quality a Tubing piping run to equipment too restrictive a Increase tubing piping diameter Refer to System Installation section for recommendations 4 Low w...

Page 19: ...19 Replacement Parts...

Page 20: ...EV307850 Support Ring EA 2 49 EV310445 Label Carbon Filter EA 1 50 EV310446 Label RO Module EA 1 51 01010248 Adaptor 3 8 Stem X 1 4 Tube EA 1 53 EV306996 Directional Arrow EA 1 No Part Number Descrip...

Page 21: ...hole punched Prints black ink on 50 offset white VENDOR MUST SUBMIT A MATERIAL CERTIFICATE OF COMPLIANCE WITH EACH SHIPMENT LET CHANGE BY APRVD DATE A DCO 4785 RH SK 9 12 02 B DCO 7060 KR RH 11 6 03 T...

Reviews: