background image

 

14 

 

Operation 

 
1.  During normal operation, a continuous supply of water must be available to the system. 
 
2.  The system inlet and outlet valves must be open, the sample outlet and flushing valves must 

be closed and the drain line must be unrestricted. 

 
3.  The outlet lines must be open to the coffee, espresso and other connected equipment. 
 
4.  Cartridge Usage Monitor 
 

The  cartridge  usage  monitor  provides  visual  indications  of  system  operation  life.  The 
device  incorporates  simultaneous  monitoring  of  system  throughput  volume  and 
operating time. This information can be used to provide more accurate determination of 
cartridge  usage  and  change-out  schedules.  Refer  to  the  instructions  provided  with  the 
module for details on programming and resetting its volume and time settings. 

 

Programmable cartridge life scales: 

 

a)  Gallonage and calendar programs act simultaneously. 
b)  A scale must be selected for both gallonage and calendar programs. 
c)  Gallonage scale is jumper selectable for 6,000, 12,000, 18,000 or 24,000 gallons. 
d)  Calendar scale is jumper selectable for 6 months or 12 months. 

 

Monitor operation: 

 

a)  “Active”  (green)  light  blinks  every  two  seconds  during  any  minimum  water  flow 

condition. 

b)  “Alert” (amber) light blinks when 80% of the programmed life scale is reached. 
c)  “Change” (red) light blinks when 100% of programmed life scale is reached.  
 
Monitor light indications: 

 

a)  The amber and green lights blink at different rates to indicate gallonage or calendar 

limits are reached. 

1. 

A single blink indicates gallonage limits have been reached. 

2. 

A double blink indicates calendar limits have been reached. 

 

Maintenance 

 
The  MRS-200  Reverse  Osmosis  system  requires  very  little  maintenance.  Regular  cartridge 
change-out  is  the  only  normal  requirement, 

and  a  very  important  one.

  The  cartridge  usage 

monitor  provides  visual  indications  once  80%  and  100%  of  selected  volume  and  calendar 
ranges are reached. 
 
In  typical  service,  the  cartridge  change-out  schedules  are  as  listed  below.  The  performance 
monitoring  instructions  below  and  the  troubleshooting  section  of  this  manual  will  help  you 
determine whether it is necessary to change cartridges on a different schedule.  

Summary of Contents for MRS-200

Page 1: ...1 Cat No EV311117 Rev B 11 6 03 DCO 7060 MODEL MRS 200 Reverse Osmosis Mineral Reduction System Installation and Start up Guide...

Page 2: ...Installation 4 Cartridge Installation and Activation 10 Start Up and Blend Adjustment 10 Adjusting the Recovery 12 Operation 14 Maintenance 14 Performance Monitoring 16 TDS Measurement 16 Performance...

Page 3: ...hlorine An activated carbon filter has been provided with this system to protect the reverse osmosis membrane from chlorine attack Influent chlorine should not exceed 3 mg L The MRS 200 System consist...

Page 4: ...nd permit access for maintenance The system will weigh approximately 175 pounds when the storage tank is full 4 ____ Does the inlet water supply meet the requirements listed below 1 A minimum of 1 0 G...

Page 5: ...nts Place the main unit on the shelf positioning the cartridge heads directly over the cutout area Insert a cable tie into one of the holes in the baseplate and through the wire slats in the shelf mak...

Page 6: ...A MP S 2 INS E RT E LB OW FULLY 3 S LIDE LOCK ING CLIP UP TO S E CURE 1 S LIDE LOCK ING CLIP DOW N Figure 3 4 Water supplies with a dynamic operating pressure of 50 PSI or less require the use of the...

Page 7: ...UMP 10 NUT 8 1 2 X 1 SPACER 4 10 X 1 1 2 SCREW 8 10 WASHER 16 MOUNTING PLATE Figure 4 5 Refer to Figure 5 for a sample general arrangement Use this as a guideline for determining valve location tubing...

Page 8: ...ow control insert red plastic cylinder in small parts kit Press this insert into the red OD tubing Fig 6 Attach the end of the tubing with the flow control insert into the 3 8 stem x OD tube reducing...

Page 9: ...lt receptacle at this time Figure 9 Figure 7 Figure 8 INLET WATER SUPPLY 50 PSIG MAX TO 120 VAC OUTLET A B C SOLENOID VALVE 1 5 2 4 3 IN A B C TO 120 VAC OUTLET SOLENOID VALVE IN COVER REMOVED 3 4 2 5...

Page 10: ...ative solution from the RO cartridge and should not be consumed 6 If you are utilizing the capillary tubing assembly refer to the section titled Adjusting the Recovery for instructions Return to this...

Page 11: ...to contain a range of TDS greater than what an RO system normally produces In those cases a filtered water blend valve has been provided to blend in filtered not RO treated water to attain a specific...

Page 12: ...product flow with a 1000 ml graduated cylinder Don t worry if the flow is slightly more or less than what is specified 2 Determine the appropriate concentrate flow for your system and the desired rec...

Page 13: ...480 70 520 80 554 10 00 50 408 60 450 70 489 80 521 12 00 50 363 60 402 70 437 80 467 14 00 50 330 60 366 70 399 80 427 16 00 50 307 60 342 70 371 80 397 18 00 50 292 60 326 70 352 80 377 20 00 50 28...

Page 14: ...or 6 000 12 000 18 000 or 24 000 gallons d Calendar scale is jumper selectable for 6 months or 12 months Monitor operation a Active green light blinks every two seconds during any minimum water flow c...

Page 15: ...s or until the water is clear 10 Close the TO flush valve 11 Connect the 24 VAC Transformer from the 115 Volt receptacle Every 6 12 months Sanitize the storage tank 1 Refer to Start up section steps 1...

Page 16: ...and a graduated cylinder or calibrated measuring cup The drain water flow rate can be measured from the end of the red tubing in a similar manner Inlet water flow Outlet Product Water Flow Drain Wate...

Page 17: ...has removed 92 of the dissolved solids from the inlet water 6 The RO cartridge should be changed every 1 to 1 1 2 years or when the percent reduction falls below 90 A form has been provided below to r...

Page 18: ...valve as required to attain specified water quality a Tubing piping run to equipment too restrictive a Increase tubing piping diameter Refer to System Installation section for recommendations 4 Low w...

Page 19: ...19 Replacement Parts...

Page 20: ...EV307850 Support Ring EA 2 49 EV310445 Label Carbon Filter EA 1 50 EV310446 Label RO Module EA 1 51 01010248 Adaptor 3 8 Stem X 1 4 Tube EA 1 53 EV306996 Directional Arrow EA 1 No Part Number Descrip...

Page 21: ...hole punched Prints black ink on 50 offset white VENDOR MUST SUBMIT A MATERIAL CERTIFICATE OF COMPLIANCE WITH EACH SHIPMENT LET CHANGE BY APRVD DATE A DCO 4785 RH SK 9 12 02 B DCO 7060 KR RH 11 6 03 T...

Reviews: