ThermalRite Blast Chiller Easy Touch Screen Manual
80
Rev02132016
Parameter
Description
Reach
In
120V
Reach
In
230V
Roll In
PR8
declared power connected to relay8
[num]
0
0
0
STB
number of cycles during D test
[num]
5
5
5
CYC
number of on7off cycles during D
test [num]
5
5
5
WIN
max pull down time in winter D test
[num]
90
90
90
SUM
max pull down time in summer D
test [num]
120
120
120
ETT
set point in heating cycle during D
test [°C/°F]
59
59
59
SPU
user set point in storage cycle
[°C/°F]
37
37
37
OF1
cabinet probe offset [num]
-0.7
-0.7
-0.7
OF2
evaporator probe offset [°C/°F]
0
0
0
OF3
condenser probe offset [°C/°F]
0
0
0
OF4
core probe point 1 offset [°C/°F]
0
0
0
OF5
core probe point 2 offset [°C/°F]
0
0
0
OF6
core probe point 3 offset [°C/°F]
0
0
0
OF7
core probe point 4 offset [°C/°F]
0
0
0
OF8
core probe point 5 offset [°C/°F]
0
0
0
SLL
not used
-40
-40
-40
SLH
not used
3
3
3
RHU
cabinet RH% set point settable
[num]
80
80
80
MNS
mains voltage alarm limit [%]
20
20
20
MAL
voltage alarm delay [hours]
10
10
10
MEV
max number of voltage conditions
before voltage alarm [num]
5
5
5
MBP
time range in which is performed
the mains voltage control [hours]
1
1
1
RL1
relay 1 action type [num]
1
1
1
RL2
relay 2 action type [num]
13
13
13
RL3
relay 3 action type [num]
17
17
17
RL4
relay 4 action type [num]
13
13
13
RL5
relay 5 action type [num]
0
0
0
RL6
relay 6 action type [num]
11
11
11
RL7
relay 7 action type [num]
10
10
10
RL8
relay 8 action type [num]
1
1
1
SRV
remaining time before maintenance
[day]
800
800
800
PCA
cabinet set point in pre-chilling
[°C/°F]
28
28
28
PCF
evaporator fan speed in pre-chilling
[num]
10
10
10
PFA
cabinet set point in pre-freezing
[°C/°F]
-22
-22
-22
PFF
evaporator fan speed in pre-
freezing [num]
10
10
10