ThermalRite Blast Chiller Easy Touch Screen Manual
Parameter
Description
Reach
In
120V
Reach
In
230V
Roll In
ADR
serial address [num]
1
1
1
EVO
alarm intervention super-parameter
[num]
0
0
0
IS1
probes and door input configuration
super-parameter [num]
155
155
155
IS2
digital input configuration super-
parameter [num]
8
8
8
IS3
not used
0
0
0
OS1
additional output super-parameter
[num]
0
0
0
OS2
additional output super-parameter
[num]
0
0
0
FOP
fans mode super-parameter [num]
131
131
131
DOP
defrost mode super-parameter
[num]
7
7
7
ALH
upper temperature alarm limit
[°C/°F]
50
50
50
ALL
lower temperature alarm limit
[°C/°F]
14
14
14
ALD
temperature alarm delay [min]
60
60
60
ADS
temperature alarm delay after start
[min]
180
180
180
ADF
temperature alarm delay after
defrost[min]
120
120
120
HYH
upper differential cooling action
[°C/°F]
2
2
2
HYL
lower differential cooling action
[°C/°F]
0
0
0
MNT
number of trays of blast chiller
[num]
15
15
15
DAC
compressor stop delay [sec]
3
3
3
ADL
minimum time of stop compressor
[sec]
60
60
60
ASS
start compressor delay at power on
[sec]
30
30
30
CON
compressor on time in probe faulty
[min]
5
5
5
COF
compressor off time in probe faulty
[min]
10
10
10
CPH
not used
90
90
90
FAS
evaporator fan set point [°C/°F]
50
50
50
HFF
differential of fan set point [°C/°F]
9
9
9
FAD
delay of fan start in evaporator
probe faulty [sec]
5
5
5
FSD
stop evaporator fan temperature in
defrost [°C/°F]
14
14
14
LBT
minimum evaporator temperature
related to set point [°C/°F]
50
50
50
EDT
choking evaporator fan
temperature range [°C/°F]
59
59
59
FEN
minimum evaporator fan speed %
[num]
25
25
25
Rev02132016