EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
2020-03-20 13:06
Pomoc Techniczna, tel.: +48 61 6500 400
26
ECO mode (unavailable in the parallel operation of UPS units).
A power saving, high efficiency mode.
If, after switching the UPS unit on in the ECO mode, the parameters of
power from the mains (voltage and frequency) meet the standard
values, receivers are powered from the mains via an internal filter.
UPS energy blocks do not take part in processing energy and
therefore this mode has high efficiency. In case of an interruption in
the mains or if power parameters of the mains exceed permissible
range, the UPS unit goes into the battery mode (the device is powered
until battery discharge or a restoration of proper power from the
mains).
The function may be activated via the LCD display (Settings menu ->
Power strategy) or by software PowerSoft. Note that the UPS
switching time between the ECO and the battery modes is about 10
ms, which may be crucial for some sensitive receivers.
Converter mode (frequency converter).
In the inverter mode, the UPS unit may freely operate with the output
frequency of 50 Hz or 60 Hz. In case of an interruption in the mains or
if the power parameters of the mains exceed permissible range, the
UPS unit goes into the battery mode and the device is continuously
powered until battery discharge or a restoration of proper power from
the mains
.
The function may be activated via the LCD display (Settings menu ->
Power strategy) or by software PowerSoft. In the converter mode the
load should be reduced to 60%.
Overload.
When the UPS unit is overloaded, an alarm signal (two short beeps
every second). The load of the UPS unit should be reduced by
disconnecting subsequent unnecessary devices.
Warning.
The appearance of the
symbol means an occurrence of
problems in unit’s operation. Such problems are usually not critical
(e.g. excessive radiator temperature). Nevertheless, pay attention to
such situations, otherwise damage may occur to the UPS unit
.
Failure.
This symbol means an occurrence of critical problems (e.g. damage of
the charging circuit). The UPS unit immediately cuts off power or
enters the bypass mode, generating continuous alarm.
Battery test.
The appearance of such symbol means that the UPS unit is running
batteries test. See chapter: "TESTING BATTERIES" for detailed
information
”.
Battery failure.
In case of a battery malfunction or disconnection, a crossed out