Instruction manual for POWERLINE RT 1-3 kVA UPS units
35
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
2016-07-13 12:09
REMOTE EMERGENCY POWER OFF (EPO) / REMOTE ON/OFF (ROO)
The triple output for connecting EPO/ROO circuits is located in the UPS unit's rear
panel - see Fig. 14.
ROO
EPO
Fig. 14: Remote power on/off circuits
In default configuration the UPS has a jumper connecting the outputs 1 and 2. These
outputs must be connected to ensure correct operation of the unit.
To use the emergency power off function remove the jumper and connect outputs 1
and 2 with a standard, zero voltage closed connector. If the connector is open the
UPS will switch off. To revert to normal operation close the connector and restart the
UPS, following the previously described procedure.
To use the remote power on/off function (ROO) connect the jumper in outputs 1 and
2 (by default, the UPS has the jumper installed) and then connect outputs 2 and 3
with a standard, zero voltage closed connector. The UPS switches off when the
connector is opened. Closing the connector restarts the UPS and powers on the
connected receivers.