EVER POWERLINE DARK 33 10 - 40 kVA UPS Operating Manual
49
Technical Assistance, phone: +48 61 6500 400
2019-06-10 14:36 Type 01
PARAMETERS \ TYPE
POWERLINE DARK 33
Model 10k
Model 15k
Model 20k
Model 30k
Model 40k
Part number
T/PWDATO-
3310K0/00
T/PWDATO-
3315K0/00
T/PWDATO-
3320K0/00
T/PWDATO-
3330K0/00
T/PWDATO-
3340K0/00
Output Power (Apparent / Active)
1)
10 kVA
10 kW
15 kVA
15 kW
20 kVA
18 kW
30 kVA
27 kW
40 kVA
36 kW
OUTPUT
Nominal output voltage
3 x 400 V AC
Output voltage range and tolerance - normal
mode
380 /400/ 415 V AC ± 1,5%
Output voltage range and tolerance - battery
mode
380 /400/ 415 V A
C ± 1,5%
Rated current
15 A
23 A
30 A
45 A
60 A
Shape of output voltage (battery mode /
normal mode)
sine-wave / sine-wave
Output voltage rated frequency
50 / 60 Hz
Output frequency range and tolerance
–
mains operation mode
Synchronously with the mains
Output frequency range and tolerance
–
battery mode
50 / 60 ± 0,1%
Output voltage regulation
± 1,5%
Output voltage distortion THDu
< 1% for Pmax (linear)
< 6% (non-linear according to PN-EN 62040-3)
Crest Factor CF
3:1
Transfer time to battery mode
0 ms
Transfer time to normal mode
0 ms
Overload capability
4)
110% - 60 min.
125% - 10 min.
150% - 1min.
>150% - 200 ms
BATTERIES AND TYPICAL RUNTIME
Internal Batteries
12 V / 7 Ah VRLA or
12 V / 9 Ah VRLA
12 V / 12 Ah VRLA
Number of internal batteries
40 (2x 20)
80 (2x 2x20
Maximum overall internal batteries capacity
9 Ah
12 Ah
External battery modules (EBM)
Yes
Maximum number of EBMs (maximum
capacity of batteries in EBM)
Depends on the maximum charging current
Backup time
– internal batteries ( 100 % / 80
% / 50 % Pmax)
Depends on the type of the used batteries
Backup time
– internal bat EBM
(100%/80%/50%Pmax)
Depends on the type and number of the used batteries
Nominal voltage DC circuit
± 240 V DC
Internal batteries maximum charging time
–
after discharging at 80 % Pmax
Depends on the type and number of batteries
Maximum charging current
3,5 A
5,3 A
6,4 A
9,6 A
12,8 A
MECHANICAL SPECIFICATIONS
Dimensions (H x W x D)
715 x 250 x 840 mm
1335 x 350 x 738 mm
1400 x 500 x 840
mm
UPS weight without internal batteries
51,5 kg
89 kg
140 kg
UPS weight with internal batteries
5)
140 kg
140 kg
177 kg
177 kg
228 kg
Transport weight - UPS without internal
batteries
63 kg
65 kg
106 kg
184 kg
Transport Dimensions (H x W x D)
930 x 400 x 990
mm
930 x 400 x 980
mm
1530 x 490 x 880 mm
1600 x 650 x
1000 mm
Position in which devices transported
Vertical
Summary of Contents for POWERLINE DARK 33 10kVA