Table 7. J6 and J7 pinout
Pin no.
Name
Description
J6-1
BCB_DRV
Output signal for triggering (disconnecting) the battery switch if
EPO is triggered or the battery is in deep discharge state. +18 V
20 mA signal is generated.
J6-2
BCB_CONT
Input signal informing about the position of the ON/OFF battery
switch.
J7-1
GND
J7-2
BCB_ONL
Input signal informing about connecting a BCB system to the
UPS. Shorting the signal from J7.1 informs the UPS about
installing the BCB system.
Battery low
The dry contact J8 terminal is used for signalling the battery charge level (low
charge). If the battery voltage is lower than the configured value, this information is
transmitted by J8 output. Depending on the NC (normally closed) or NO (normally
open) configuration, changing the state to the other one means the battery charge is
low. Fig. 33 presents the manner of making the connection. Table 8 presents the
pinout and the relevant description.
Fig. 33: Connections for J8 terminal
Table 8. J8 pinout
Pin no.
Name
Description
J8-1
BAT_LOW_NC
Relay informing about low battery voltage -
normally closed (J8-1 and J8-3). An open relay
indicates a warning about low battery voltage.
J8-2
BAT_LOW_NO
Relay informing about low battery voltage -
normally closed (J8-2 and J8-3). A closed relay
indicates a warning about low battery voltage
J8-3
GND
Common for NO and NC