EVER POWERLINE DARK 33 10 - 40 kVA UPS Operating Manual
Type 01 2019-06-10 14:36
Technical Assistance, phone: +48 61 6500 400
46
dependent on the changing load. If the changes of the generator's voltage frequency
exceed the designed tolerance, the UPS identifies such frequency as incorrect and
switches to a relevant operating mode, as per the previously described principles of
operation.
STORAGE, MAINTENANCE AND TRANSPORT
The UPS should be stored and transported in conditions conforming to the
installation guidelines covered in a separate document attached to the UPS. If these
requirements are not satisfied, EVER Sp. z o.o. will not be liable for any mechanical
damage arising during transportation.
CAUTION:
The procedure of securing the system before transportation
should be carried out by qualified personnel, experienced in handling
batteries and using proper safety measures. Only authorized personnel
should have access to batteries.
As a part of preventive maintenance, the area around the UPS should be kept clean.
The device should be vacuum cleaned if the air is highly polluted with dust.
To ensure maximum battery life, ambient temperature around the operating UPS
units should be 15-
25 ºC.
CAUTION:
The operating life of the battery depends on the frequency
and manner of use, as well as on the ambient temperature. The designed
operating life of the batteries used in the UPS is 3-5 years. After that time,
the capacity, reliability and, consequently, the operating time of the
batteries will be heavily reduced. A battery should be replaced every 5
years to guarantee it’s top efficiency.
CAUTION:
Batteries should be replaced by qualified technicians,
experienced in handling batteries and following proper safety precautions.
CAUTION:
The UPS and the batteries should be stored in dry, well
ventilated rooms.