POWERLINE 11 series UPS – Instruction Manual
2011/07/22
www.ever.eu
23
BATTERY BACK-UP AND POWER GENERATORS
The POWERLINE series battery back-ups are ONLINE-class devices. By design, the
battery back-up tolerates mains voltage variations in the range of ~176÷276V, as well
as frequency variations of ±4 Hz with respect to the nominal frequency of 50 Hz.
When working with a power generator, the frequency of the generator’s voltage is
variable and strictly dependent on the load value changes. If the frequency value
exceeds tolerance limits, the back-up will deem it incorrect and switch into battery
operation mode.
STORAGE, MAINTENANCE
The battery back-up should be stored in a cool and dry place, in operating position,
with accumulators completely charged:
•
In temperature between 0°C and +30°C the accumulat or should be charged every
6 months;
•
In temperature between +30°C and +45°C the accumul ator should be charged
every 3 months.
DISPOSAL
Appropriate disposal of used up electric and electronic equipment helps to avoid
consequences resulting from the presence of dangerous materials, as well as
inappropriate storage and processing of such equipment, which may be hazardous to
human life and the environment.
Act dated 29 July 2005 on used up electric and electronic equipment, article 22.1
items 1 and 2.
According to the regulations binding in the European Union, a
crossed rubbish bin symbol means that when a product is no
longer used it should be disposed of at a special waste pickup site.
This concerns the device itself, as well as other accessories
marked with this symbol. Do not dispose of those products
together with unsorted household waste.
Method of safe removal of the batteries from the appliance:
The batteries should be removed from the appliance by an authorised service outlet
or by a duly authorised electrician.