7.Standard default value 

(Factory preset settings)

10

8.Setting value range

a. Pressure setting range : 0.01 ~ 10.00bar

b. Time-Delay setting range : 0 ~ 60 seconds

c. Detection time after Dry-running setting range: 1~120 seconds

d. Time of automatic re-start running after warning shutdown

    (α value) setting range : 0 ~ 600 seconds

e. Auto shutdown setting range: None and 0.5~5Hours

a. Max. pressure value : 2.5 kg/cm²

b. Min. pressure value : 1.5 kg/cm²

c. Delay Time when reaching the Max. Pressure : 15 seconds

d. The pressure unit : kg/cm²

e. Detection time of water shortage : 30 seconds

f.  Pressure of water shortage : 0.5 kg/cm²

g. Time of automatic re-start running after warning shutdown  

     (α value) : 60 seconds

h. Auto shutdown setting after continuous running : St-0

i.  Over pressure value is fixed in 10bar and cannot modify

-

-

dF-n

dF-y

-

-

- - - -

or

loAd

Restore to 

default value 

setting

LCD screen 

display “loAd” 

or “ ----” for 3 

seconds to 

store and finish 

the setting

a.Select to restore default value settings 

(dF-y), press the right button and adjust the  

parameter value from dF-n to dF-y.  

After finishing the setting, press the SET  

button, then all the advanced value 

settings are returned to default value. 

LCD screen will display "- - - -" for 3 seconds 

and return to the current pressure conditions.

b.Stay on this screen for 30 seconds, the

   display screen will automatically return to 

   the current pressure conditions and the

   preset data value will not be stored.  

c.Choose not to return to default value 

settings (dF-n), select dF-n and press the 

SET button again, LCD screen display 

"loAd" for 3 seconds and will 

return to the 

After LCD screen displaying “loAd” or “ ----”

for 3 seconds, above setting value is stored

and it will automatically return to the current

pressure value.      

6

7

Item Parameters Display

Code

Default

Unit

Data

Range

Description

 

current pressure conditions automatically. 

9.The current operating parameters display

1).Max. pressure setting display 

(high pressure) (Show code P-max)

2).Min. start pressure setting display

 (low pressure) (Show code P-min)

↓ Press             once

a-1. Press          once to browse original pressure value 

↓ Press             once

3).Pressure of water shortage setting display (Dry running) 

    (Show code P-Dry)

↓ Press              again

Summary of Contents for DPC-10

Page 1: ... lation and Operation Manual EVAK PUMP TECHNOLOGY CORP No 551 Zhongshan Rd Qingshui Dist Taichung City 436 Taiwan TEL 886 4 26233556 Fax 886 4 26235559 11 Warning Assemble tool Do not poke the port Do not pull the cable Wire conductors must not be exposed to avoid any shortage from the conductor end WARNING ...

Page 2: ...lay Technical Data Button Pressure Unit Relay Capacity 1HP in 110V or 2HP in 230V The digital pressure controller can control pump with higher output through a contactor with control circuit voltage of 110Vac or 230Vac in the other hand the supply voltage to DPC is 110Vac or 230Vac 50 60hz please refer to the wiring diagram for requirement Dry Running Digital Pressure Controller DPC 10 Over Pressu...

Page 3: ...the voltage is over 250V please add transformer by yourself DPC 10 Controller Gray Brown Blue Black AC 230V M1 Coil DPC 10 Controller Gray Brown Blue Black 1 phase PUMP WARNING WARNING WARNING Any connection to the contactor please add a R C capacitor spark eliminator to reduce the possible electromagnetic interference WARNING Beware of any connection to the contactor Please add a R C capacitor sp...

Page 4: ...o the current pressure conditions and the preset data value will not be stored c Choose not to modify the delay time press the SET button and LCD display loAd The above setting value is stored and after 3 seconds will automatically return to the current pressure value 2 3 4 setting 0 01 10 00 5 The status of LED lights 6 Parameter display and settings Item Light Message indication Control loop off...

Page 5: ...ing 2 3 0 600 sec hour Auto Reset Auto Time setting of automatic re start running after warning shutdown Dry running or Over pressure α value Auto shutdown setting after continuous running a Select to modify automatic re start time press the left or right button to adjust the value after finishing the setting press the SET button and go to next parameter setting The time of automatic re start auto...

Page 6: ...e right button and adjust the parameter value from dF n to dF y After finishing the setting press the SET button then all the advanced value settings are returned to default value LCD screen will display for 3 seconds and return to the current pressure conditions b Stay on this screen for 30 seconds the display screen will automatically return to the current pressure conditions and the preset data...

Page 7: ...ss for 6 seconds to Lock Unlock the SET button 1 Max pressure setting high pressure Show code P max b Press once to enter basic setting Press to adjust the value upward Press to adjust the value downward 2 Min Start pressure setting low pressure Show code P min Press once Press to adjust the value upward Press to adjust the value downward Press once ...

Page 8: ...stored Show code loAd c Press for 3 seconds to enter advanced setting Press to adjust the value upward Press to adjust the value downward Press once 3 seconds later 5 After finishing above setting 3 seconds later will return to the current pressure status display automatically Press to set up unit Cycle of working pressure unit kg cm psi bar kg cm Press once ...

Page 9: ...tdown Dry running or Over pressure α value Show code Auto reset Press to adjust the value upward Press to adjust the value downward Press once Press to adjust the value upward Press to adjust the value downward Press once St 0 Pressure controller keeps running and will not automatically shut down St 5 St 1 5 Pressure controller will auto shut down after continuously running 0 5 or 1 5 hours and wi...

Page 10: ... 6 Restore to default value setting or not To restore default value settings show code dF y Press to adjust the value to dF y Press once and restore to default value Show code 7 After finishing above settings LCD screen display loAd or 3 seconds later above setting value is stored and it will automatically return to the current pressure value Not to restore default value settings show code dF n Pr...

Reviews: