“              ” Hold down for 3 seconds (Advanced setting Mode)

Item Parameters Display

Code

Default

Unit

Data

Range

Unit

-

-

Description

Switch the 

display working 

pressure unit 

a.Select to switch the Unit of working 

pressure, press the right button to change 

the pressure unit (Cycle : kg/cm² 

→ Psi 

→ bar → 

kg/cm²), then press the SET 

button once and go to next parameter    

setting. 

b.Stay on this screen for 30 seconds, the

   display screen will automatically return to 

   the current pressure conditions and the

   preset data value will not be stored.  
c.Choose not to modify the working pressure 

unit, press the SET button once, and go 

to next parameter setting.

1

P-Dry

sec 1~120

0.01~

10.00

P-Dry

Detection time

setting of water

shortage

Pressure of 

water shortage 

setting 

(Dry running)

a.Select to modify the detection time after 

reaching the pressure setting of water 

shortage (Dry running), press the left or 

 

right button to adjust the value, after 

b.Stay on this screen for 30 seconds, the

   display screen will automatically return to 

   the current pressure conditions and the

   preset data value will not be stored.  

c.Choose not to modify P-Dry detection time 

setting, press the SET button once, and 

go to next parameter setting.

a.Select to modify the Pressure of water 

shortage, press the left or right button to 

adjust the value, after finishing the setting, 

press the SET button and go to next 

b.Stay on this screen for 30 seconds, the

   display screen will automatically return to 

   the current pressure conditions and the

   preset data value will not be stored.  
c.Choose not to modify the pressure of water 

shortage, press the SET button, and go

to next parameter setting.

2

3

0~600

sec

hour

Auto

Reset

Auto

Time setting of 

automatic 

re-start running 

after warning 

shutdown (Dry 

running or 

Over pressure) 

(

α

 value)

Auto shutdown

 setting after 

continuous 

running

a.Select to modify automatic re-start time, 

press the left or right button to adjust the 

value, after finishing the setting, press the SET 

button, and go to next parameter setting.  

The time of automatic re-start = (automatic 

time setting) x (trip times)³

(Cumulative trip times is up to 10 times, if  

pressing the right button to re-start, then the 

trip times can be re-calculated.)

b.Stay on this screen for 30 seconds, the

   display screen will automatically return to 

   the current pressure conditions and the

   preset data value will not be stored.  

c.Choose not to modify the automatic re-start 

time, press the SET button, and go to next 

parameter setting.

a.Select to modify the auto shutdown setting 

   after continuous running, press the left or 

   right button to adjust the value, after finish-

   ing the setting, press the SET button and 

   go to next parameter setting.
 

  St-0: 

Pressure controller keeps running 

   and won’t shut down automatically.

  St-.5: 

Pressure controller will auto shut 

   down after continuously running 0.5 hours 

   and won’t auto restart after the shutdown.

   

St-1~5: 

Pressure controller will auto shut 

   down after continuously running 1~5 hours 

   and won’t auto restart after the shutdown.

4

5

finishing the setting, press the SET button  

kg/cm²

parameter setting.

Item Parameters Display

Code

Default

Unit

Data

Range

Description

and go to next parameter setting. 

St-0

St-.5

St-1

~

St-5

b.Stay on this screen for 30 seconds, the

   display screen will automatically return to 

   the current pressure conditions and the

   preset data value will not be stored.  

c.Choose not to modify the automatic re-start 

time, press the SET button, and go to next 

parameter setting.

08

Summary of Contents for DPC-10

Page 1: ... lation and Operation Manual EVAK PUMP TECHNOLOGY CORP No 551 Zhongshan Rd Qingshui Dist Taichung City 436 Taiwan TEL 886 4 26233556 Fax 886 4 26235559 11 Warning Assemble tool Do not poke the port Do not pull the cable Wire conductors must not be exposed to avoid any shortage from the conductor end WARNING ...

Page 2: ...lay Technical Data Button Pressure Unit Relay Capacity 1HP in 110V or 2HP in 230V The digital pressure controller can control pump with higher output through a contactor with control circuit voltage of 110Vac or 230Vac in the other hand the supply voltage to DPC is 110Vac or 230Vac 50 60hz please refer to the wiring diagram for requirement Dry Running Digital Pressure Controller DPC 10 Over Pressu...

Page 3: ...the voltage is over 250V please add transformer by yourself DPC 10 Controller Gray Brown Blue Black AC 230V M1 Coil DPC 10 Controller Gray Brown Blue Black 1 phase PUMP WARNING WARNING WARNING Any connection to the contactor please add a R C capacitor spark eliminator to reduce the possible electromagnetic interference WARNING Beware of any connection to the contactor Please add a R C capacitor sp...

Page 4: ...o the current pressure conditions and the preset data value will not be stored c Choose not to modify the delay time press the SET button and LCD display loAd The above setting value is stored and after 3 seconds will automatically return to the current pressure value 2 3 4 setting 0 01 10 00 5 The status of LED lights 6 Parameter display and settings Item Light Message indication Control loop off...

Page 5: ...ing 2 3 0 600 sec hour Auto Reset Auto Time setting of automatic re start running after warning shutdown Dry running or Over pressure α value Auto shutdown setting after continuous running a Select to modify automatic re start time press the left or right button to adjust the value after finishing the setting press the SET button and go to next parameter setting The time of automatic re start auto...

Page 6: ...e right button and adjust the parameter value from dF n to dF y After finishing the setting press the SET button then all the advanced value settings are returned to default value LCD screen will display for 3 seconds and return to the current pressure conditions b Stay on this screen for 30 seconds the display screen will automatically return to the current pressure conditions and the preset data...

Page 7: ...ss for 6 seconds to Lock Unlock the SET button 1 Max pressure setting high pressure Show code P max b Press once to enter basic setting Press to adjust the value upward Press to adjust the value downward 2 Min Start pressure setting low pressure Show code P min Press once Press to adjust the value upward Press to adjust the value downward Press once ...

Page 8: ...stored Show code loAd c Press for 3 seconds to enter advanced setting Press to adjust the value upward Press to adjust the value downward Press once 3 seconds later 5 After finishing above setting 3 seconds later will return to the current pressure status display automatically Press to set up unit Cycle of working pressure unit kg cm psi bar kg cm Press once ...

Page 9: ...tdown Dry running or Over pressure α value Show code Auto reset Press to adjust the value upward Press to adjust the value downward Press once Press to adjust the value upward Press to adjust the value downward Press once St 0 Pressure controller keeps running and will not automatically shut down St 5 St 1 5 Pressure controller will auto shut down after continuously running 0 5 or 1 5 hours and wi...

Page 10: ... 6 Restore to default value setting or not To restore default value settings show code dF y Press to adjust the value to dF y Press once and restore to default value Show code 7 After finishing above settings LCD screen display loAd or 3 seconds later above setting value is stored and it will automatically return to the current pressure value Not to restore default value settings show code dF n Pr...

Reviews: