Product-manual Model: 635/DER u. 635/K DER
07-01-05-06-E-V1002.doc
45
5.6
Fuses, contactors, filters
Compact Units
635/
K DER01.A3
635/
K DER03.A3
635/
K DER05.A3
635/
K DER07.A3
635/
K DER10.A3
max. contious Input-
Current
[Aeff]
[A
RMS
]
4 (1-ph)
2 (3-ph)
6,5 (1-ph)
4 (3-ph)
11 (1-ph)
6,5 (3-ph)
14 (1-ph)
8 (3-ph)
10 (3-Ph)
Recommended Line-Fuses and Contactors
RCD-Switch
not recommendet. Required setpoint: 300 mA
Mains protection
1)
T10A
T10A
T10A
T20A
T20A
protector-switch
2)
PKZM0-16
PKZM0-16
PKZM0-16
PKZM0-16
PKZM0-16
Mains contactor
2)
DIL 00M
DIL 00M
DIL 00M
DIL 00M
DIL 00M
Line Filters
general
only for use earth referenced supplies(TN). Current – drain to PE !
single-phase
industrial env.
Max motorcable.50m
(EN55011 A)
3) model
LNF S 1*230/012
or LNF E 1*230/012
residential env.
Max motorcable.20m
(EN55011 B)
3) model
LNF S 1*230/012
oder LNF E 1*230/012
3-phase
industrial env.
max motorcable.50m
(EN55011 A)
model
LNF B 3*480/008
LNF K
3*480/018
residential env..
max motorcable.50m
(EN55011 B)
3) model
LNF B 3*480/008
LNF K
3*480/018
3-phases, several servo-drives supplied by one common filter
industrial env.
max motorcable.20m
(EN55011 A)
4) model
LNF B 3*480/018; LNF B 3*480/033
other models on request
(according to ref.measurements with 3 units, supplied by common line)
residential env.
max motorcable.20m
(EN55011 B)
3)
4)
model
LNF B 3*480/018; LNF K 3*480/033
other models on request
(according to ref.measurements with 3 units, supplied by common line)
1) recommended for UL-requirements: Bussmann Type FRS-R, 600V, use only UL-approved fuse-holders !
2) recommended, Klöckner Moeller for instance
3) Toroidal Ferrit, Eurotherm-model FR required at motor cable near to the drive.
4) Measurement of conducted emissions only.
Plug-in modules
635/
DER 01.A3
635/
DER 03.A3
635/
DER 05.A3
635/
DER 07.A3
635/
DER 10.A3
max. contious
Input-Current
1-phase
3-phase
[Aeff]
[A RMS]
4
2
6,5
4
11
6,5
1
8
10
Fuses, Contactors, Filters
general
Orientation: Table for Compact-Units and the addition of rated currents of used
units on the DC-Bus. Depending on the application, energy-sharing effects by DC-
Link may reduce the required supply-current considerable
Fuses
Rule of the Thumb: 1,5 to 2 times of added rated currents
Power-On-Peaks
Depending on Power-Supply-Unit, Limiting equipment is requiered
(Delay-Contactor)
only for use in earth referenced supplies(TN). Current-Drain to PE !
Filter types
Orientation: Table of Compact-Units. Further Types: see separate manual
Summary of Contents for 635
Page 63: ...Product manual Model 635 DER u 635 K DER 07 01 05 06 E V1002 doc 63 10 Block circuit diagram ...
Page 72: ...72 Product manual Model 635 DER u 635 K DER 07 01 05 06 E V1002 doc 14 Certificates ...
Page 73: ...Product manual Model 635 DER u 635 K DER 07 01 05 06 E V1002 doc 73 Certificates ...
Page 74: ...74 Product manual Model 635 DER u 635 K DER 07 01 05 06 E V1002 doc Certificates ...
Page 75: ...Product manual Model 635 DER u 635 K DER 07 01 05 06 E V1002 doc 75 Certificates ...
Page 77: ...Product manual Model 635 DER u 635 K DER 07 01 05 06 E V1002 doc 77 16 Notes ...