SETTABLE FUNCTIONS
Dynamic Set Point
The unit's controller enables automatic modification of the set point according to the inlet air temperature conditions.
This modification is obtained by varying the set point by a value depending on the outside air temperature measured
by the probe AT .
The parameters defining the compensation line are:
The function can be enabled/disabled with parameter C01
It is then necessary to define the compensation characteristic through the remaining parameters .
The maximum variation foreseen for the set point is defined with parameter C02 .
The set point variation slope is defined with parameter C03 .
The temperature below which compensation must start is defined with parameter C04 .
The figure opposite shows the meaning of the parameters .
Disinfection cycles
It is possible to set the tank water disinfection cycles . These cycles are recommended in case of prolonged
permanence of the water at a temperature below 60 °C
The parameters defining the disinfection cycles are:
The function can be enabled/disabled with parameter C01
It is then necessary to define the compensation characteristic through the remaining parameters .
The maximum variation foreseen for the set point is defined with parameter C02 .
The set point variation slope is defined with parameter C03 .
The temperature below which compensation must start is defined with parameter C04 .
The figure below shows the meaning of the parameters .
INSTALLATION
Parameter code
Description of parameter
Default value
Range of settable values
C01
Enable compensation
0
0-No\1-YES
C02
Compensation offset
5°C
1 ~ 10°C
C03
Compensation factor
-1 °C\°C
-5 ~ 5 °C\°C
C04
Compensation start temperature
5°C
-30 ~ 30°C
Parameter code
Description of parameter
Default value
Range of settable values
g01
Disinfection temperature
60°C
30 ~ 70 °C
g02
Disinfection cycle duration
0 min
0 ~ 90 min
g03
Disinfection start time
0 h
0 ~ 23 h
g04
Days between disinfection cycles
7 D
7 ~ 99 D
C02
C04
Temperatura aria
Temperatura
set point
Valore di
riferimento
Massimo
valore
raggiungibile
C03
g01
Tempo
Temp
acqua °C
g02
g04
g03
Water
temp °C
Fig .2
Fig .3
Reference
value
Max . value
reachable
Set point
temperature
Air temperature
Time