background image

EUROSTER 2006TXRX 

 INSTALLATION AND OPERATION MANUAL

 

7

 

 

6.10.

 

FLOOR SENSOR CONNECTION 

a.

 

Check if J1 jumper is in the floor position (point 4.4.) 

b.

 

Connect the floor sensor to terminals No. 4 and 5 in the thermostat. 

c.

 

Reset the thermostat. 

d.

 

The thermostat operates according to floor sensor indications. The range of controlled 

temperature increases to 45°C. 

The standard temperature sensor is inactive. 

7.

 

RX RECEIVER SETTINGS 

7.1.

 

Establishing  a  connection  between  2006TX  thermostat  with  RX  receiver  or 
receivers (pairing) 

Each  thermostat  and  each  receiver  has  a  unique  number  distinguishing  it  from  other 
thermostats.  It  is  not  possible  for  any  thermostat  not  paired  with  the  particular  receiver  to 
interfere with the operation of another pair or set. 
The  thermostat  may  be  paired  with  other  receivers  at  any  time.  Neither  a  blackout,  battery 
replacement  nor  a  complete  reset  of  all  thermostat  settings  affects  the  pairing  of  devices  in 
any way. 
Pairing procedure: 

 

RESET button (under the front cover), 

 

remove the thermostat housing, 

 

press the button on the transmitter plate three times 

 the signaling LED starts flashing 

alternately in red and green,  

 

 

 

insert the RX receiver to the power socket,  

 

press the receiver button 3 times 

 blue signaling LED lights up, 

 

when the connection is established the blue LED switches off, 

 

if one receiver only is used, press the transmitter button, the LED switches off. Pairing 
mode is completed. 

If several (maximum 6) receivers are to be paired: 

 

After detection of the first receiver, 

 

Insert the second receiver to the power socket 

 

Press the receiver button 3 times 

 blue signaling LED lights up 

 

After detection of the first receiver, the blue LED switches off 

 

Follow the same steps to connect the subsequent receivers, then press the transmitter 
button. Pairing mode is completed. 

Note! 

Pairing  mode  is  only  available  for  10  minutes  after  connecting  the  receiver  to  the 
mains,

 

restoring factory settings and inserting batteries into the thermostat! 

Factory-established  thermostat

receiver  pairs  are  paired;  however,  pairing  may  be 

repeated if necessary.

 

7.2.

 

Selection of operating mode 

While keeping the button 

“B”

 pressed insert the receiver into the power socket. Depending on 

the preset mode green or red LED lights up. Each pressing of the button changes the operating 
mode. After a mode is selected, the receiver restores operation. 

Summary of Contents for 2006TXRX

Page 1: ...ture and economical night temperature Each temperature may be modified within the range of 5 35 C The thermostat is programmable in seven day cycles with an accuracy of 0 5 hour therefore it enables 4...

Page 2: ...when programming a thermostat 7 8 Multi purpose setting buttons increase decrease DISPLAY 9 Temporary change of temperature MANUAL sign is displayed to indicate that the temperature has been changed m...

Page 3: ...r liquids Do not install any units showing signs of mechanical damage The thermostat is not a safety component Additional protection devices must be used in systems prone to the risk of damage due to...

Page 4: ...the thermostat while observing the correct polarity There are installation markings in the battery compartment Then install snap the thermostat onto the base The battery indicator will be visible whe...

Page 5: ...C or 1 C d After five seconds the setting is stored and the device restores operation 6 4 TEMPERATURE READOUT CORRECTION a Set the knob in the MON position b Simultaneously press and hold for 3 sec H...

Page 6: ...HOLD 6 8 5 C FROST PROTECTION SETTING a Set the knob in the START position b Press HOLD and hold it for 5 sec A F letters appear on the display c Frost protection function is activated Regardless of...

Page 7: ...imes the signaling LED starts flashing alternately in red and green insert the RX receiver to the power socket press the receiver button 3 times blue signaling LED lights up when the connection is est...

Page 8: ...ication If the communication between the thermostat and the receiver is interrupted e g discharged batteries and such status lasts for 2 minutes no response from the receiver then the receiver switche...

Page 9: ...a soft cloth 11 DIMENSIONS 12 TECHNICAL DATA Controlled device heating air conditioning systems Supply voltage 3 V 2 pieces of alkaline AA batteries receiver 230 V 50 Hz Thermostat output relay volta...

Page 10: ...d out wheelie bin symbol Fig 1 The batteries are subject to selective collection in accordance with the provisions of the Directive 2006 66 EC of the European Parliament and of the Council Such markin...

Page 11: ...ce 4 The device may be repaired exclusively by the manufacturer or by a party clearly authorized by the manufacturer 5 Warranty becomes void in case of any mechanical damage incorrect operation and re...