EUROSTER 11WB User Manual Download Page 5

EUROSTER 11WB 

 USER MANUAL 

 

5

 

 

1.

 

Boiler target temperature for CH operation

 

It  is  the  temperature  of  the  boiler  to  be  maintained  by  the  controller.  In  case  of 
operation in the DHW priority mode, the controller can maintain a higher temperature 
to heat up the tank.

 

2.

 

Hysteresis of the blower operation

 

This  is  a  temperature  range  in  which  the  controller  linearly  adjusts  the  blower  power. 
The narrower the temperature range, the smaller the system temperature fluctuations. 
However, a too narrow range may result in the temperature oscillation 

 the controller 

will alternately heat up and cool down the boiler. 
At the time of installation, set the maximum hysteresis value. Wait for the installation 
temperature to reach a stable value. If, under such conditions, the blower operates at a 
power level between settings No. (3) and (4), the hysteresis may be reduced.

 

3.

 

Minimum power of the blower

 

This is the lowest power at which the blower may operate. It should be set at minimum 
value  at  which  the  blower  rotor  starts  to  rotate.  This  value  should  be  selected 
experimentally using the blower test function (setting No. 16).

 

4.

 

Maximum power of the blower

 

This  is  the  highest  power  at  which  the  blower  may  operate.  The  value  should  be 
selected  experimentally so that the boiler temperature maintained by the  controller is 
as close to the preset temperature as possible.

 

5.

 

Blow-through time

 

This is a period of the blower operation in the blow-through mode. The blower is turned 
on in order to remove combustion gases from the boiler. The blow-through time should 
be  long  enough  to  effectively  exhaust  the  gases  via  the  stack  and  short  enough  to 
prevent the boiler temperature rise.

 

6.

 

Time interval between successive blow-throughs

 

This is the time passing between the end of the blow-through cycle and the start of a 
new cycle. It should be set so that to prevent the boiler temperature rise, but on the 
other hand to avoid explosive combustion of the gases generated in the boiler.

 

7.

 

DHW tank temperature

 

This is an average DHW tank temperature to be maintained by the controller.

 

ATTENTION: Maintaining a low temperature in the tank (at a level of 35-40 

°C) 

facilitates the development of bacterial flora, including Legionella. 

8.

 

Hysteresis of the DHW tank pump

 

Difference  between  the  temperature  at  which  the  pump  is  turned  off  and  turned  on, 
provided  that  the  boiler  is  hot  enough  to  enable  heating  of  the  tank  (taking  setting 
No. 9 into account). 
The conditions of turning the pump on and off are specified in section 13.

 

9.

 

Boiler and tank differential temperature

 

This is the value by which the boiler temperature should exceed the tank temperature 
(plus the constant parameter of 3 

°C) to enable filling of the tank without a risk that it 

will chill out. Alternately, in case of increase of the DHW tank temperature or decrease 
of 

the 

boiler 

temperature 

this 

differential 

value  

(minus  the  constant  parameter  of  3 

°C)  specifies  the  temperature  at  which  the  filling 

cycle will be interrupted.

 

10.

 

DHW heating priority

 

Activation of the DHW priority results in faster heat up of the cold DHW tank, by turning 
the CH pump off and increasing the boiler preset temperature. 
After  heating  up  of  the  tank  to  the  desired  temperature,  the  controller  resumes  to 
normal operation. 
If the DHW priority is turned off, the DHW pump is started when the tank temperature 
is low and the boiler temperature is high enough. 

 

11.

 

CH pump operation temperature

 

The conditions of turning the pump on and off are specified in section 13.

 

12.

 

CH pump hysteresis

 

This is a differential temperature at which the controller turns the pump on and off. 
The conditions of turning the pump on and off are specified in section 13.

 

Summary of Contents for 11WB

Page 1: ...he operation of the CH and DHW circulation pumps EUROSTER 11WB controller is equipped with an Anti Stop function that prevents seizing of an idle pump rotor It automatically turns the pumps on for 30...

Page 2: ...point specially designed for that purpose or on an unshielded outlet pipe of the CH boiler as close to the boiler as possible fix the DHW sensor on the tank point specially designed for that purpose...

Page 3: ...t while the temperature is manually adjusted 4 Alarm icon blinks in case of alarm 5 Furnace status display see the description below 6 Blower icon lit at the time of blower operation 7 DHW pump icon l...

Page 4: ...g 1 restores factory settings bl Backlight will be displayed and once the knob is released 0 will appear Use the knob to select the required number 0 or 1 and confirm Selecting 0 results in automatic...

Page 5: ...sing between the end of the blow through cycle and the start of a new cycle It should be set so that to prevent the boiler temperature rise but on the other hand to avoid explosive combustion of the g...

Page 6: ...ump calculated by the controller 0 or 1 Press the knob to activate testing of the output Press the knob again or leave it inactive for 10 seconds to resume automatic operation 18 CH pump operation tes...

Page 7: ...tically resume the normal operation mode i e the pumps will not be turned off 11 FUELING Turn the blower off for the time the furnace is loaded with new fuel For this purpose turn the knob all the way...

Page 8: ...g the tank down provided that the temperature of the heat source exceeds the tank temperature by at least the value of the preset Difference 9 plus 3 C T boiler T tank T difference 3 The pump cannot b...

Page 9: ...ower Controller emits a buzzing sound Loose coils in the interference filter does not impact the correct operation of the device Controller knob operates erratically Pulse generator damage send the de...

Page 10: ...voltage may result in increased energy losses in the pumps and in the fan and contribute to malfunction of the whole system 20 KIT CONTENTS a controller with 2 temperature sensors b sensor hose clips...

Page 11: ...the device would not meet your requirements any more you are kindly requested to have it brought in to an electronic waste management facility Electronic waste is collected free of charge by local dis...

Page 12: ...ly by the manufacturer or by other party clearly authorized by the manufacturer 5 Warranty becomes invalidated in case of any mechanical damage incorrect operation and or making any repairs by unautho...

Reviews: