Overheating 

 the furnace temperature > 90 

°C

 

 <-> 

 

Shutdown 

  failure  to  reach  the  preset  temperature  of  the  boiler  within  an  hour  or  the 

temperature of the furnace dropped below the shutdown temperature (setting No. 15). 

 

7.

 

TURNING THE CONTROLLER ON 

 

Turn the controller power switch (7) into the "I" position. 

 

A  device  firmware  version  number  and  its  compilation  date  are  sequentially  displayed 
for 2 seconds after turning on. 

 

The ANTI-STOP function turns the pumps on for 30 seconds 

 

“AS” letters are blinking 

on the display. 

 

The system status is presented at the display. 

 

Adjust the controller settings when turning the controller on for the first time (section 
9). 

8.

 

RESTORING FACTORY SETTINGS / PERMANENT LIGHT-UP OF THE DISPLAY 

Proceed as follows to restore factory settings, if needed: 

 

Keep the knob pressed and turn the controller off and on. 

"Fd"

 (Factory defaults) will 

be displayed and once the knob is released, 0 will appear.  

 

Use the knob to select the number (0 or 1) and confirm. 
Selecting  0  enables  to  change  screen  backlight  functions  without  restoring  factory 
defaults. Selecting 1 restores factory settings. 

 

"bl"

 (Backlight) will be displayed and once the knob is released, 0 will appear. 

 

Use the knob to select the required number (0 or 1) and confirm. Selecting 0 results in 
automatic screen backlight switch off after 1 minute of finishing operating the controller, 
and selecting 1 results in permanent backlight of the display. 

 

Control and possibly correct the remaining controller settings. 

In  case  of  lack  of  confirmation  within  5 seconds,  the  controller  resumes  operation  without 
introducing changes. 

9.

 

CONTROLLER SETTINGS 

After being switched on the controller shows the system status. Turn the knob right to enter 
the setting preview and change mode. 
The controller configuration is specified below: Turn the knob in order to choose the required 
parameter.  The  controller  will  show  the  value  (at  the  top)  and  number  (at  the  bottom).  In 
order to change the value of the displayed parameter, push the knob (the parameter value will 
start  blinking),  set  the  required  value  and  confirm  the  selection  by  pressing  the  knob.  If  the 
current value should not be changed (cancellation of changes), do not push the knob, but wait 
10 seconds for the setting to stop blinking. 
Setting windows are numbered for convenient operation of the controller. 
The user can change the following parameters:

 

Summary of Contents for 11WB

Page 1: ...he operation of the CH and DHW circulation pumps EUROSTER 11WB controller is equipped with an Anti Stop function that prevents seizing of an idle pump rotor It automatically turns the pumps on for 30...

Page 2: ...point specially designed for that purpose or on an unshielded outlet pipe of the CH boiler as close to the boiler as possible fix the DHW sensor on the tank point specially designed for that purpose...

Page 3: ...t while the temperature is manually adjusted 4 Alarm icon blinks in case of alarm 5 Furnace status display see the description below 6 Blower icon lit at the time of blower operation 7 DHW pump icon l...

Page 4: ...g 1 restores factory settings bl Backlight will be displayed and once the knob is released 0 will appear Use the knob to select the required number 0 or 1 and confirm Selecting 0 results in automatic...

Page 5: ...sing between the end of the blow through cycle and the start of a new cycle It should be set so that to prevent the boiler temperature rise but on the other hand to avoid explosive combustion of the g...

Page 6: ...ump calculated by the controller 0 or 1 Press the knob to activate testing of the output Press the knob again or leave it inactive for 10 seconds to resume automatic operation 18 CH pump operation tes...

Page 7: ...tically resume the normal operation mode i e the pumps will not be turned off 11 FUELING Turn the blower off for the time the furnace is loaded with new fuel For this purpose turn the knob all the way...

Page 8: ...g the tank down provided that the temperature of the heat source exceeds the tank temperature by at least the value of the preset Difference 9 plus 3 C T boiler T tank T difference 3 The pump cannot b...

Page 9: ...ower Controller emits a buzzing sound Loose coils in the interference filter does not impact the correct operation of the device Controller knob operates erratically Pulse generator damage send the de...

Page 10: ...voltage may result in increased energy losses in the pumps and in the fan and contribute to malfunction of the whole system 20 KIT CONTENTS a controller with 2 temperature sensors b sensor hose clips...

Page 11: ...the device would not meet your requirements any more you are kindly requested to have it brought in to an electronic waste management facility Electronic waste is collected free of charge by local dis...

Page 12: ...ly by the manufacturer or by other party clearly authorized by the manufacturer 5 Warranty becomes invalidated in case of any mechanical damage incorrect operation and or making any repairs by unautho...