29
2126330-10-03/21 (translation of the original operating instructions)
Operating Instructions Safety Systems
MGB-L..B-EI-… (Ethernet/IP) and With Data Structure Type A
EN
17. Special functions
17.1. Factory reset
1. Switch off the MGB.
2. Set all DIP switches to ON.
3. Restart the MGB.
4. Wait for the LED flashing code.
5. Switch off the MGB.
6. Set DIP switches based on the required configuration (see the table
DIP switch assignment on page 21
).
7. Switch on the MGB.
NOTICE
The factory reset clears all set customer configurations such as IP address, network mask and gateway
settings. This does not apply to the learned data of the locking module such as the learned handle
module or number of operating cycles.
17.2. Software update
The MGB firmware can be updated using the
ControlFLASH™
software
1)
from
Rockwell Automation
. New firmware updates
are available from the EUCHNER support team. Refer to
Rockwell Automation Manual 1756-UM105J
for more details about
using
ControlFLASH
.
1)
ControlFLASH is a trademark of Rockwell Automation, Inc.