12. Controls and indicators
Lock
DIA
State
Power
Act 2
Lnk 2
Net
Mod
Pwr
Lnk 1
Act 1
X1
X4
X3
X2
LEDs on locking/release module
see System status table
Cover for DIP switch-
es
LEDs on the bus module
LED
Color
Meaning
ACT1
ACT2
OFF
Green flashing
Yellow flashing
No activity
Port activity
Collision
LNK1
LNK2
OFF
Green
Yellow
Red
No connection
Connection
Port disabled
Major NIC fault
NET
Green flashing
Green
Red flashing
Red
Red/green flashing
No network connection
Network connection
Timeout
Communication failed
Network error
LED
Color
Safety Super-
visor Status
Meaning
MOD
OFF
No voltage
No voltage
Green
Version
Normal operation
Green flashing
Idle
Idle or ready
Check the Identity and
the Safety Supervisor
Object.
Red flashing
Cancel
Resettable fault
Red
Critical fault
Non-resettable fault
Red/green
flashing
Self-test,
waiting for
TUNID
or
configuration
Self-test/Power On
Device must be
configured or TUNID
is missing, incomplete
or incorrect. Check
the Identity Object
and the Safety Super-
visor Object.
A detailed overview of the error messages can be found in
chapter
15. MGB system diagnostic messages on page 27
.
3
6
1
2
5
1
2
3
4
4
3
6
1
2
5
1
2
3
4
4
n.c.
DHCP
IP-Bit 7
IP-Bit 6
IP-Bit 5
IP-Bit 4
IP-Bit 3
IP-Bit 2
IP-Bit 1
IP-Bit 0
OFF ON
ON OFF
DIP switch assignment
Switch
Designation
Val-
ue
Function
Block 2
1
n.c.
Reserved
2
DHCP
OFF position = IP address via DIP switch
ON position = IP address via DHCP
(attention: all other DIP switches in
position = OFF)
Tip:
Set the DIP switch to ON to identify your MGB in the
control system. This will ensure that the device is recognized
by the DHCP server. This can be helpful if you do not know
the IP address.
3
IP bit 7
128 Enter the last byte of the IP address bit by bit here.
4
IP bit 6
64
Example:
192.168.1.[DIP switch code, binary]
|----------------------|
Fixed part
The following applies:
OFF position
= 0
ON position = 1
Notice
:
Different
IP addresses
according to data
sheet are possible.
5
IP bit 5
32
6
IP bit 4
16
Block 1
1
IP bit 3
8
2
IP bit 2
4
3
IP bit 1
2
4
IP bit 0
1
(Factory setting: all switches in OFF position)
Connection for EUCHNER enabling switch ZSA
(order no. 110560)
Fig. 16:
Indicators and control elements