10.5. Maximum cable lengths
Switch chains are permitted up to a maximum overall cable length of 200 m taking into account the voltage drop as a result
of the cable resistance (see table below with example data and case example).
SPS
PLC
l
1
l
2
l
max
=200 m
l
n
u
min
= 24 V -10%
u
n
= 24 V -20%
5 x 0,34 mm
2
CET-AR # n
CES-AR # n-1
CES-AR # 1
i
out
n
Max. number of switches
I
OA/OB
(mA)
Possible output current per channel OA/OB
l
1
(m)
Max. cable length from the last switch to the
control system
5
10
150
25
100
50
80
100
50
200
25
6
10
120
25
90
50
70
100
50
200
25
10
10
70
25
60
50
50
100
40
200
25