7.3. Escape release (optional)
Permits opening of a locked guard from the danger zone without tools (see chapter
mension drawing for safety switch CET.‑AR‑… on page 44
).
The safety outputs are switched off when the escape release is actuated. Use the safety
outputs
to generate a stop command
.
The monitoring output OUT is switched off; OUT D can assume an undefined state. Open the guard
and close it again after resetting the escape release. The device will then operate normally again.
Important!
Ì
It must be possible to actuate the escape release manually from in-
side the protected area without tools.
Ì
It must not be possible to reach the escape release from the outside.
Ì
The actuator must not be under tensile stress during manual release.
Ì
The escape release meets the requirements of Category B according
to EN ISO 13849-1:2015.
7.3.1. Actuating escape release
Press the red release knob to the stop.
¨
Guard locking is released.
Pull the knob out again to reset.