9.3. Functional check
After installation and any fault, the safety function must be fully checked. Proceed as follows:
WARNING
Danger of fatal injury as a result of faults in installation and functional check.
Ì
Before carrying out the functional check, make sure that there are no persons in the danger zone.
Ì
Observe the valid accident prevention regulations.
1. Switch on operating voltage.
Ì
The safety switch carries out a self-test.
The green STATE LED flashes for 3 s at 10 Hz.
The green STATE LED then flashes at regular intervals.
2. Close all guards.
Ì
The machine must not start automatically.
Ì
The green STATE LED illuminates continuously.
3. Enable operation in the control system.
4. Open the guard.
Ì
The machine must switch off and it must not be possible to start it as long as the guard is open.
Ì
The green STATE LED flashes at regular intervals.
Repeat steps 2-4 for each guard.