Non-Contact Safety Switch CES-AH-C03-AE-LS
EN
For channel A:
Ì
Voltage drop on the switch
D
U
1
= R x I = 250 m
W
x 1 A = 250 mV
Ì
Voltage drop on the cable
D
U
2
= R
l
x s x I = 25 m
W
/m x 10 m x 1 A = 250 mV
Ì
Voltage at the load
U = U
B
-
D
U
1
-
D
U
2
= 24 V - 0.25 V - 0.25 V = 23.5 V
For channel B:
Ì
Voltage drop on the switch
D
U
1
= R x I = 250 m
W
x 4 A = 1 V
Ì
Voltage drop on the cable
D
U
2
= R
l
x l x I = 25 m
W
/m x 8 m x 4 A = 800 mV
Ì
Voltage at the load
U = U
B
-
D
U
1
-
D
U
2
= 24 V - 1 V - 0.8 V = 22.2 V
8.8. Connecting cables and plug connectors
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connecting cables.
Ì
Use EUCHNER connectors.
Ì
If other connection components are used, the following recommendations apply. EUCHNER pro-
vides no warranty for safe function in case of failure to comply with these requirements.
Ì
The maximum cable length should not exceed 50 m.
Recommended connecting cable
:
e.g. LiYY 7 x 1mm²,
Ölflex classic 400P 7 x 0.75
Terminating plug for the mating side
:
AMP Superseal series, manufacturer Tyco/AMP
Component
AMP order number
Required quantity
Socket contact
(for conductor cross-sections 0.75 ... 1.5
mm²)
183025-1
7
Socket housing 3-pin
282087-1
1
Socket housing 4-pin
282088-1
1
Individual core seals
depending on core diameter:
Total 7
1.4 ... 1.7 mm
green
281934-4
1.8 ... 2.4 mm
yellow
281934-2
2.6 ... 3.3 mm
red
281934-3
Important!
It is imperative you use the original tools from the connector manufacturer for assembly and follow
the assembly instructions from the connector manufacturer.