Operating Instructions
Non-Contact Safety Switch CES-AH-C03-AH-SM
24
(Translation of the original operating instructions) 106595-09-06/20
11.5.2. Operating distances
Actuating range for center offset m = 0
(only in combination with actuator CES-A-BPA on surface mounting)
Parameter
Value
Unit
min.
typ.
max.
Operating distance
-
22
1)
-
mm
Assured operating distance s
ao
18
-
-
Switching hysteresis
1
2
-
Assured release distance s
ar
-
-
58
1) On surface mounting on aluminum; the typical operating distances increase to 30 mm in a non-metallic environment.
Typical actuating range
(only in combination with actuator CES-A-BPA on surface mounting)
45
40
35
30
25
20
15
10
-45
5
Z
Y
X
5
10
15
20
25
30
35
40
45
45
40
-45
35
30
25
20
15
10
5
For a side approach direction for the actuator and read head, a minimum distance of s = 6 mm must be maintained so that the
actuating range of the side lobes is not entered.
Figure 5:
Typical actuating range