For channel B:
Ì
Voltage drop on the switch
D
U
1
= R x I = 250 m
W
x 3.5 A = 0.875 V
Ì
Voltage drop on the cable
D
U
2
= R
l
x l x I = 25 m
W
/m x 10 m x 3.5 A = 0.875 V
Ì
Voltage at the load
U = U
B
-
D
U
1
-
D
U
2
= 24 V - 0.875 V - 0.875 V = 22.25 V
8.8. Connecting cables and plug connectors
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connecting cables.
Ì
Use EUCHNER connectors.
Ì
If other connection components are used, the following recommendations apply. EUCHNER pro-
vides no warranty for safe function in case of failure to comply with these requirements.
Ì
The maximum cable length should not exceed 50 m.
Recommended connecting cable
:
e.g. LiYY 7 x 1mm²,
Ölflex classic 400P 7 x 0.75
Mating connector for the evaluation unit
:
EUCHNER M23, 9-pin, conductor cross section. max. 1 mm² order no. 106 597
Alternative, e.g.
Coninvers order no. RC-09S1N121600, cable cross-section max. 1 mm²
Important!
It is imperative you use the original tools from the connector manufacturer for assembly and follow
the assembly instructions from the connector manufacturer.