106595-09-06/20 (Translation of the original operating instructions)
Operating Instructions
Non-Contact Safety Switch CES-AH-C03-AH-SM
EN
11.2. Typical system times
Refer to the technical data for the exact values.
Ready delay:
After switch-on, the device carries out a self test. The system is ready for operation only after this time.
Risk time according to EN 60947-5-3:
If an actuator moves outside the actuating range, the safety outputs (OA and
OB) are deactivated at the latest after the risk time.
Difference time:
The safety outputs LA and LB switch with a slight time offset. They have the same signal state no later
than after the discrepancy time.
System times for
restart after fault
and
normal operation
Example application: UB = 24 V
+LA permanently connected to UB
+LB switched by control system
t
Actuator
Start
LA
+LB
LB
DIA (LED red)
Off
On
0 V
+24 V
0 V
+24 V
0 V
+24 V
+LA
0 V
+24 V
0 V
+24 V
None
Detected
Star
t
Fault detection
Occurr
ence of a fault
Restar
t
Star
t
Operational
No actuator
Ausgänge schalten aus
Star
t connected together
Actuator detected
∆
t
1
∆
t
2
∆
t
3
∆
t
4
D
t
1
= Fault detection time
D
t
2
= Fault time (5 s; switch dwells in the fault state during this time)
D
t
3
= Power-up time (3 s)
D
t
4
= Risk time (
≤
260 ms, time from
no actuator
to
outputs switch off
)
Figure 3:
System times for individual switches