G R O U N D I N G   I N S T R U C T I O N S  
Etrel  INCH  DUO  charging  station  needs  to  be  properly 

grounded  to  allow  safe  use.  In  the  case  of  malfunction 

or  breakdown,  grounding  provides  protective  measure 

to reduce the risk of electric shock.  
Multiple  grounding  system  are  supported:  TN-S,  TN-C, 

TN-C-S, and TT.  
Improper  connection  of  the  equipment  (grounding 

conductor)  may  result  in  risk  of  electric  shock.  Check 

with a qualified electrician or service person if you are in 

doubt as to whether the product is properly grounded.  

E L E C T R I C I T Y   P R O T E C T I O N   E L E M E N T S  
Overvoltage protection: The device is a Class 2 appliance 

and  must  be  protected  with  an  upstream  overvoltage 

protection.  
Overcurrent protection: Should be installed upstream to 

protect power supply cable and the charging device. 
Differential protection: Should be installed separately if 

not  already  built  in  the  charger.  A  dedicated  residual 

current  device  (RCD)  device  must  be  used according  to 

applicable regulations. 

E N V I R O N M E N T   O P E R A T I N G   R A N G E  
The device achieves at least IP 54 level of protection. It 

can be used outdoors and indoors if environment meets 

following constraints: 

 

Elevation < 2000 m above sea level. 

 

Temperature range from -25 °C to +65 °C. 

 

Non-condensing max. humidity 95%.  

E Q U I P M E N T   N E E D E D  

 

Phillips screwdriver, 

 

hex screwdriver, 

 

utility knife, 

 

crimping pliers for cable end sleeves, 

 

wire strippers and cable rippers. 

Summary of Contents for INCH DUO

Page 1: ...Ver 2021 3 EN Etrel INCH DUO QUICK START GUIDE EN...

Page 2: ......

Page 3: ...ersions of international standards The charging station is compliant with IEC 61851 Part 1 Part 21 2 Part 22 international standard which defines conductive AC electric vehicle charging and supports M...

Page 4: ...trical codes legislation and ordinances Warning Before installing and wiring the charging station make sure that the power supply is disconnected remove fuses or deactivate the circuit breaker to prot...

Page 5: ...ible that not all modules are part of an actual device LTE module Frequency bands LTE FDD B1 2100 MHz B3 1800 MHz B5 850 MHz B7 2600 MHz B8 900 MHz B20 800 MHz LTE TDD B38 2600 MHz B40 2300 MHz B41 25...

Page 6: ...lass 2 appliance and must be protected with an upstream overvoltage protection Overcurrent protection Should be installed upstream to protect power supply cable and the charging device Differential pr...

Page 7: ...g steel to the concrete foundation to enable construction of a larger foundation 1 b The foundation anchor must be assembled before installation Tighten the two nuts to each end of each rod 6 times In...

Page 8: ...addition it needs to be temporarily clogged with paper or similar material at both ends so that the concrete cannot enter the pipe 4 When pouring concrete it is first poured into the vicinity of the...

Page 9: ...20 mm of insulation from all cables and attach and compress the appropriate crimp tubes on all cables To prevent cables from getting in the way of mounting the charging station twist them into an ins...

Page 10: ...rt all three phase conductors and the neutral N conductor into the circuit breaker terminals and tighten them firmly Attach the supply ground PE cable to the earthing clamp 8 b When charging station i...

Page 11: ...g station may affect the measurement results or be damaged if tested with higher voltage Before closing the station check the condition of the over current protection elements and the residual current...

Page 12: ...te or for troubleshooting please look at https etrel com charging solutions inch duo www etrel com Etrel d o o Pod jel ami 6 1290 Grosuplje Slovenia EU 2020 Etrel All rights reserved Etrel the Etrel l...

Reviews: