 8    |   10 

 

 

Removing the Power Supply Cover 

The  safety  cover  protects  against  accidental  direct 

contact  with  live  parts. Turn  off  the  main  power  before 

removing  the  cover.  Unscrew  the  screws  and  then 

remove the cover. 

 

Earthing 

Attach earthing cable to the screw of the foundation and 

tighten it tightly with a sixth nut. Attach the other end of 

the cable to the PE clamp. Connect the earthing strip to 

the PE clamp as well.  

 

 

8-a 

 

Connecting Power Supply Cables 

Remove the sticker with designation of conductors. 
Slightly loosen the screws on the underside of the circuit 

breaker  terminal  and  on  the  earthing  clamp,  located 

right.  
Insert  all  three  phase  conductors  and  the  neutral  (N) 

conductor into  the  circuit breaker terminals and tighten 

them  firmly.  Attach the  supply  ground  (PE)  cable  to  the 

earthing clamp. 

 

8-b 

When  charging  station  is  part  of  a  cluster  of  charging 

stations,  configuration with additional  clamps  should be 

ordered. In this case connect all three phase conductors 

(ingoing  and  outgoing)  to  the  cluster  clamps  first  to  be 

able to connect other charging stations. 

 

 

Closing the Power Supply Cover 

Place  the  power  supply  cover  in  the  appropriate  place 

and tighten it with screws. 

 

10 

Preparation of Communication Cable 

In  the  case  of  a  LAN  connection,  cut  the  cable  to  the 

appropriate  length  so  that  it  can  be  connected  to  the 

Ethernet  port.  It  is  recommended  to  use  an  UTP  Cat  6 

shielded  cable  that  is  resistant  to  interference  from 

nearby power cords.  

Summary of Contents for INCH DUO

Page 1: ...Ver 2021 3 EN Etrel INCH DUO QUICK START GUIDE EN...

Page 2: ......

Page 3: ...ersions of international standards The charging station is compliant with IEC 61851 Part 1 Part 21 2 Part 22 international standard which defines conductive AC electric vehicle charging and supports M...

Page 4: ...trical codes legislation and ordinances Warning Before installing and wiring the charging station make sure that the power supply is disconnected remove fuses or deactivate the circuit breaker to prot...

Page 5: ...ible that not all modules are part of an actual device LTE module Frequency bands LTE FDD B1 2100 MHz B3 1800 MHz B5 850 MHz B7 2600 MHz B8 900 MHz B20 800 MHz LTE TDD B38 2600 MHz B40 2300 MHz B41 25...

Page 6: ...lass 2 appliance and must be protected with an upstream overvoltage protection Overcurrent protection Should be installed upstream to protect power supply cable and the charging device Differential pr...

Page 7: ...g steel to the concrete foundation to enable construction of a larger foundation 1 b The foundation anchor must be assembled before installation Tighten the two nuts to each end of each rod 6 times In...

Page 8: ...addition it needs to be temporarily clogged with paper or similar material at both ends so that the concrete cannot enter the pipe 4 When pouring concrete it is first poured into the vicinity of the...

Page 9: ...20 mm of insulation from all cables and attach and compress the appropriate crimp tubes on all cables To prevent cables from getting in the way of mounting the charging station twist them into an ins...

Page 10: ...rt all three phase conductors and the neutral N conductor into the circuit breaker terminals and tighten them firmly Attach the supply ground PE cable to the earthing clamp 8 b When charging station i...

Page 11: ...g station may affect the measurement results or be damaged if tested with higher voltage Before closing the station check the condition of the over current protection elements and the residual current...

Page 12: ...te or for troubleshooting please look at https etrel com charging solutions inch duo www etrel com Etrel d o o Pod jel ami 6 1290 Grosuplje Slovenia EU 2020 Etrel All rights reserved Etrel the Etrel l...

Reviews: