Reminder C25 HMI :
1.
Source 1 availability information (Green fixed when source 1 is present and available within threshold limits, green
blinking when source 1 is present but outside of threshold limits, off when under 50VAC).
2.
Switch 1 LED position indication (Green fixed when in position 1).
3.
Zero position LED indication (Yellow when in position 0).
4.
Load supplied information (Green fixed when load is supplied by an available source)
5.
Switch 2 LED position indications (Green fixed when in position 2).
6.
Source 2 availability information (Green fixed when source 2 is present and available within threshold limits, green
blinking when source 2 is present but outside of threshold limits, off when under 50VAC).
7.
Auto LED indication (Green fixed when in automatic, blinking when a transfer is ongoing, off when in manual mode
or inhi- bited or fault is ongoing).
8.
Test LED (Yellow fixed when test on load is ongoing).
9.
Configurations dip switches (8 dip switches with 2 positions A and B see chapter 7.5 for configuration details).
10.
Run LED (Green when product is powered).
11.
COM LED (yellow blinking when RS communications is ongoing).
12.
Fault LED (Red blinking
– long blink when fault or product in inhibited, fast blink when a dip switch parameter
has been changed and needs validation).
13.
Fire (Red when fire input is activated).
Summary of Contents for 004661922
Page 1: ...EN INSTRUCTION MANUAL ATSC25 ATS Controller www eti eu support...
Page 25: ...EN 25 11 2 Connection diagrams 11 2 1Connections with MLBS 4P 63 125...
Page 26: ...26 EN 11 2 2Connections with standard Contactors CEM and CES...
Page 27: ...EN 27 11 2 3Connections with MCCBs EB2 and MO2...
Page 34: ......