22
EN
10. TROUBLE SHOOTING GUIDE
DEFINITION
RECOMMENDED ACTION
Sources are not detected
- Verify that the product is correctly powered on using the power LED.
- Verify that the DIP switch settings are corresponding to your installation.
Positions are not detected
-Verify that the position input cabling is correctly done.
Source LED are blinking
- Verify that the sources are in the voltage range configured through DIP switch or
communication.
- Verify that the sources are cabled correctly.
- Verify that the phase rotation.
Alarm LED is blinking
- Verify that the input 63-64 is closed.
- Verify that there has not been a problem during a transfer order and validate fault
with the AUTO button.
-Verify that the DIP switches have not changed position or validate the change of
position using the RES button.
COM LED is on fixed
- Verify that Communication settings are set according to your specification.
-
Press “RES” for 30 seconds to reset the Communication settings.
- Contact ETI for other information.
DIP switch parameters are not
taken into account
- Check if the alarm LED is blinking.
- Verify that you are in manual mode when changing DIP switch parameters.
-
Press the “RES” button for less than 3s to validate the parameter change.
Summary of Contents for 004661922