EW50 Industrial LTE Cellular Gateway
157
Sniffer & Full-Time Proxy
: This is a mixed mode for both Sniffer and Full-Time
Proxy modes.
Master Type
IP Address
is selected
by default.
Specify the Modbus master device to apply with the data logging rule. It can be
IP Address
for Modbus TCP master, or
Local Serial Port
for local attached
Modbus RTU/ASCII master.
Master Query
Timeout (sec.)
1. Optional setting.
2.
60
sec is set by
default
3. Range 1 to 99999
Specify the timeout value for querying the Modbus Master. If there is no
response from the master within the specified timeout setting, the selected
proxy rule will be triggered and applied with the data logging rule.
Note: If Off-Line proxy scheme is selected, the timeout setting will be used to
check. Otherwise, this value is not used.
Proxy Rules
Optional setting.
Select the Proxy rule to be applied with the data logging rule.
Note: If any proxy scheme is selected, please create the required Proxy rules in
advance, and select from the list.
Enable
Unchecked by default.
Check the box to activate the data logging rule.
Save
N/A
Click the
Save
button to save the settings.
Undo
N/A
Click the
Undo
button to cancel the changes.