Gas Supply Piping

When measuring the inlet supply pressure, the water heater and all other gas appliances sharing the gas supply 
line must be 

 ring at maximum capacity. 

Maximum gas pressure must not exceed listed value.
Low gas pressure could be caused by an undersized gas pipe; this will cause the water heater's performance to 
diminish and it would not be able to reach maximum performance.


Size gas piping system correctly by following ANSI Z223.1/NFPA 54, or by local code.

Based on 0.60 specific gravity for natural gas at 0.5" W.C. pressure drop DOE standard is 1000 BTU per cubic ft. of natural gas

Based on 0.60 specific gravity for natural gas at 3.0" W.C. pressure drop; 

8.0" W.C. or greater supply pressure

. DOE standard 

is 1000 BTU per cubic ft. of natural gas

Gas Piping System Codes

NATURAL GAS SUPPLY PIPING

NATURAL GAS SUPPLY PIPING

A manual gas control valve (shut-off valve) must be connected to the unit before the gas line.
Check the gas inlet pressure and make sure the type of gas matches matching the rating plate located on 
your water heater. Also, check to make sure your gas meter is capable of supplying suf

 cient BTU load to all 

appliances. Insuf

 cient gas pressure and volume will cause your water heater to be de

 cient in performance 

and may not work properly.
When  connections  are  completed,  check  for  gas  leaks  by  applying  soapy  water  to  all  gas  fittings  and 
connections. Presence of soap bubbles foaming is a sign of gas

 

leak. 

This  appliance  and  its  individual  shut-off  valve  must  be  isolated  from  the  gas  supply  piping  system  by 
unplugging the unit and turning off the main gas valve during any pressure testing of the gas supply piping 
system at test pressures equal to or less than 1/2 PSI.

NOTICE

!

!

Pipe 

Cubic Feet of Natural Gas

size

Length

10

20

30

40

50

60

70

80

90

100

125

150

200

1/2"

172

118

95

81

72

65

60

56

52

50

44

40

34

3/4"

360

247

199

170

151

137

126

117

110

104

92

83

71

1"

678

466

374

320

284

257

237

220

207

195

173

157

134

1 1/4"

1390

967

768

657

583

528

486

452

424

400

355

322

275

1 1/2"

2090

1430

1150

985

873

791

728

677

635

600

532

482

412

2"

4020

2760

2220

1900

1680

1520

1400

1300

1220

1160

1020

928

794

Pipe 

Cubic Feet of Natural Gas

size

Length

10

20

30

40

50

60

70

80

90

100

125

150

200

1/2"

454

312

250

214

190

172

158

147

138

131

116

105

90

3/4"

949

552

524

448

397

360

331

308

280

273

242

219

188

1"

1787

1228

986

844

748

678

624

580

544

514

456

413

353

1 1/4"

3669

2522

2025

1733

1536

1392

1280

1191

1118

1056

936

848

726

1 1/2"

5497

3778

3034

2597

2302

2085

1919

1785

1675

1582

1402

1270

1087

2"

10588

7277

5844

5001

4433

4016

3695

3437

3225

3046

2700

2446

2094

Based on 1.50 specific gravity for propane gas at 0.5" W.C. pressure drop; 11" W.C. supply pressure

PROPANE GAS SUPPLY PIPING

Pipe 

KBTU of Propane Gas

size

Length

10

20

30

40

50

60

80

100

125

150

175'

200

1/2"

291

200

160

137

122

110

101

94

89

84

74

67

3/4"

608

418

336

287

255

231

212

197

185

175

155

140

1"

1150

787

632

541

480

434

400

372

349

330

292

265

1 1/4"

2350

1620

1300

1110

985

892

821

763

716

677

600

543

1 1/2"

3520

2420

1940

1660

1480

1340

1230

1140

1070

1010

899

814

2"

6790

4660

3750

3210

2840

2570

2370

2200

2070

1950

1730

1570

Summary of Contents for GU125T

Page 1: ...Only specially trained and authorized personnel are permitted to service this water heater NOTE TO ASSEMBLER INSTALLER Leave this manual with the consumer NOTE TO CONSUMER Keep this manual for future...

Page 2: ...l Horizontal Termination P20 21 Clearance Requirements from Vent Terminations to Building Openings P22 Multiple Units Termination P23 Vent Pipe Installation Terminator Position P24 Gas Supply Piping P...

Page 3: ...3 Included Accessories Optional Accessories...

Page 4: ...5 000 BTU Hr 100 000 BTU Hr Gas Supply Pressure NG LP 3 5 WC to 10 5 WC 8 WC to 14 WC Ignition System Direct Electronic Ignition w Automatic Flame Sensing Burner System Sealed Combustion with Metal Fi...

Page 5: ...5 Dimensions GU125T 518 11 12 1125 GU160T 518 11 12 1160...

Page 6: ...6 Dimensions GU125T 518 11 12 1125 GU160T 518 11 12 1160...

Page 7: ...7 Dimensions GU125T 518 11 12 1125 GU160T 518 11 12 1160...

Page 8: ...9 Exhaust Adaptor 152320028 20 Trap Clamp 151010032 21 Condensate Trap 332070125 22 Intake Air Pressure Switch 192320116 GU125T 192290098 GU160T 23 Exhaust Air Pressure Switch 192320117 GU125T 1922900...

Page 9: ...quali ed service technician to inspect the water heater and to replace any damaged parts Far away from water heater In approved containers Tightly closed Out of children s reach Cannot be seen Vapors...

Page 10: ...supply line and the result of thermal expansion can create a rapid and dangerous pressure increase in the water heater and system piping This rapid pressure increase can quickly reach the safety sett...

Page 11: ...5 feet with one 90 elbow If more elbows are required the venting distance must be reduced 5 feet for every 90 elbow Condensation may be created at times as the combustion gases exit the vent cap Disco...

Page 12: ...lation procedure Insert condensate trap into the exhaust adaptor and install trap clamp Place exhaust pipe inside exhaust adaptor socket bottom Then hold the exhaust pipe in place by attaching the pip...

Page 13: ...tighten water pipe with pipe wrench Use Spanner to fix gas adaptor and then tighten gas pipe with pipe wrench Use spanner to fix valve and then tighten T P valve with pipe wrench Water Pipe Installati...

Page 14: ...g area CAUTION The condensate drain line material must be an approved material by the authority having jurisdiction In absence of such authority PVC and CPVC piping must comply with ASTM D1785 or D284...

Page 15: ...use of a condensate pump Size the pump to allow for a maximum condensate discharge of 2 GPH from the water heater Horizontal runs must be sloped 1 4 per foot towards the drain or condensate pump Be s...

Page 16: ...ll appliances in the enclosed area When combustion air is supplied from inside the building each opening should give a minimum free area of one square inch per 1 000 Btu hour of the total input rating...

Page 17: ...accordance with the above provisions should comply with NFPA 720 and be ANSI UL 2034 listed and CSA certified Signage A metal or plastic identification plate should be permanently mounted to the exter...

Page 18: ...ng Systems ULC S636 Components of this listed system shall not be interchanged with other vent systems or unlisted pipe ttings All plastic components and speci ed primers and glues of the certi ed ven...

Page 19: ...ve intake open How To Con gure Unit For Power Vent Maximum Allowable Vent and Combustion Air Piping Length 3 inch Piping Feet Max of 90 elbows 100 6 Reduce the maximum allowable length for each elbow...

Page 20: ...Operation manual WARNING Through roof Power Vent Minimum twelve 12 inches above anticipated snow level The termination cannot be connected to an existing vent piping or chimney The total vertical and...

Page 21: ...vent pipe or ttings with mortar or silicone caulk silicone caulk as show above Complete the rest of the vent pipe installation to the water heater s vent connector tting on the blower outlet If necess...

Page 22: ...When Heater is Installed Indoors Maintain the following clearances to any opening in any building 4 below 4 horizontally from or 1 above any door operable window or gravity air inlet into any building...

Page 23: ...mportant to avoid recirculation of flue gases Concentric Multivent Termination Horizontal Terminations Vertical Terminations Multiple Unit Termination Vertical Terminations Horizontal Terminations The...

Page 24: ...Clearance to each side of center line extended above meter regulator assembly 3 feet within a height 15 feet above the meter regulator assembly I Clearance to service regulator vent outlet 3 feet J C...

Page 25: ...ividual shut off valve must be isolated from the gas supply piping system by unplugging the unit and turning off the main gas valve during any pressure testing of the gas supply piping system at test...

Page 26: ...nded sizing of piping tanks and 100 lockup gas regulator NOTICE 5 Prior to start up ensure the unit is set to re propane Check the rating label for the type of fuel If there is a con ict or doubt on t...

Page 27: ...aining valve from the unit and clean the lter FILLING THE WATER DRAINING THE WATER Close the water heater drain valve by turning the knob to the right The drain valve is on the lower right side of the...

Page 28: ...o protect from power surges Do not connect 220 240V AC to this unit It will damage the water heater and void the warranty Do not disconnect the power supply when the unit is in normal operation A batt...

Page 29: ...red properly and compliant to Local and State Codes Pump control such as aquastat or timer must be used in recirculation applications or long burner runtime occur and cause premature failure Daily usa...

Page 30: ...emperature delivered Contact a licensed professional for maintenance NOTICE Once the unit has been properly installed check the gas and water connections for leaks Check for proper ventilation and com...

Page 31: ...ature should not be set higher than 120 F Please check with your local codes to ensure temperature is set properly CAUTION BURN 1 To switch the water heater ON from OFF condition press the Power Butto...

Page 32: ...water insects rodents or other foreign materials such as fallen leaves and dust that could cause blockages Do not obstruct the ow of combustion air and exhaust air ow Water Strainer The water strainer...

Page 33: ...tory and more Diagnostic Contents Example Explanation Outlet temperature Ot Ot 134 Outlet temperature is 134 F Hot water stored tank temperature Ht Ht 145 Tank temperature is 145 F Fan RPM Rp Rp 4500...

Page 34: ...hout a service call Please quote the code displayed when inquiring about service NOTE In all cases you may be able to clear the Error Message simply by turning the hot water tap OFF then ON again If t...

Page 35: ...35 Wiring and Connection Diagram Wiring Diagram MODEL GU125T 518 11 12 1125 GU160T 518 11 12 1160...

Page 36: ...not apply when the Product is used with recirculation system for hot water on demand is installed unless external aquastat or timer controls and a thermal expansion tank are installed and properly and...

Page 37: ...isregarding Grand Hall sizing recommendations power or direct venting with air intake exposed to contaminated environment solely closed loop space heating applications and uncontrolled or improperly s...

Page 38: ...38 The stand assembly installation manual...

Page 39: ...39 The stand assembly installation manual...

Reviews: