DSC2P Hardware Manual
ETEL Doc. - Hardware Manual # DSC2P / Ver H / 6/1/11
3.7.1.2
The motor cable
Caution:
In order to respect the EMC standard, the following motor connector must be used.
Remark:
The cable's radius of curvature must be taken into account to adjust the distance between the
front plate of the controller and the cabinet.
If a motor cable with a small diameter is used, turn the metallic clamp over to maintain the shield
continuity
3.8
Axis number selection
It is possible to assign or to change the axis number of the controller with a DIP switch. After each starting, the
controller takes the axis number given by the DIP switch except when all the white switches are in the high
position which means set to 1 (like in the picture below). In this case the axis number is set by the AXI command
or the value previously saved in the controller or by the default value always equal to 1 (this default value is
used when no AXI command has been executed or no save has been done).
Example:
The value given on the DIP switch represents a binary value. As the switch number
6 is not used, there are 32 possibilities. The axes are numbered from 0 to 30
because the axis 31 is reserved for the DSMAX.
The axis number given by this DIP switch is equal to: 2
0
+ 2
1
= 3.
Shield contact
on 360°
Metallic cable clamp
Screws connecting the motor
connector to the front panel
of the controller
60.6 mm
36
.1
8 mm
30°